Figure 4-17. ECU Setup

A

ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, or MTU ECU7.

B

Speed Select: Primary or Secondary.

C

Accelerator Position: Adjustable from 0 to 100% in 1% increments.

D

MDEC Module Type: CAN Module 201, 302, 303, or 304.

E

Speed Demand Switch: Analog CAN, Up Down ECU, Up Down CAN, Analog ECU, Frequency, No

CAN Demand.

F

Engine RPM: Adjustable from 1,400 to 2,000 in increments of 1.

G

Overspeed Test: Off or On.

H

Governor Param Switch Over: Off or On.

I

Trip Reset: Press to set.

J

Int Oil Prime: Press to set.

K

Speed Up: Press to set.

L

Speed Down: Press to set.

M

Speed Demand Limit: Off or On.

N

Increased Idle: 0 to 1,000 in increments of 1.

O

Engine Start Prime: Off or On.

P

Fan Override: Off or On.

Q

Mode Switch: Off or On.

R

Governor Param Set Select: 0 to 1,000 in increments of 1.

S

CAN Rating Switch 1 & 2: Off or On.

T

Cylinder Cutout Disable 1 & 2: Off or On.

Modem Setup (Optional)
DGC-2020 controllers with style number xxxxxMxxx are equipped with an internal telephone modem that
has dial-in and dial-out capability. The modem gives the DGC-2020 the ability to dial up to four telephone
numbers

A

and annunciate user-selected conditions to specified pagers

B

. These user-selected conditions

include

C

:

 27-1 Trip Alarm

 27-2 Trip Alarm

 32 Trip Alarm

 40 Trip Alarm

 47 Trip Alarm

 51-1 Trip Alarm

 51-2 Trip Alarm

 51-3 Trip Alarm

 59-1 Trip Alarm

 59-2 Trip Alarm