Programmable senders, Programmable senders -64, Figure 4-59. network configuration settings -64 – Winco DGC-2020 User Manual

Page 134

Advertising
background image

BESTCOMSPlus network configuration settings (DGC-2020, Multigen Management, Network
Configuration) are illustrated in Figure 4-59.

Figure 4-59. Network Configuration Settings

A

Expected Seq Id: Adjustable from 0 to 255.

PROGRAMMABLE SENDERS

The sender inputs of the DGC-2020 can be customized to obtain maximum accuracy from the coolant
temperature, oil pressure, and fuel level senders.
The characteristic curve of each sender input can be configured with up to 11 points

A

. Each point can be

assigned a resistance input value and a corresponding temperature (coolant temperature sender),
pressure (oil pressure sender), or percentage (fuel level sender) value. A sender slope setting

B

automatically orders the values in the resistance column according to whether the sender requires a
negative or positive slope. Sender curve points are automatically plotted on a curve

C

in BESTCOMSPlus,

which can be printed

D

.

Sender curve points configured in BESTCOMSPlus can be saved in the configuration file

E

. The data for

all three senders is automatically saved with the DGC-2020 configuration file.
Any changes made in BESTCOMSPlus to the sender points, can be reverted to the factory-default
values

F

. A new settings file can also be created

G

.

BESTCOMSPlus programmable sender settings (DGC-2020, Programmable Senders, Coolant
Temperature, Oil Pressure, or Percent Fuel Level) are illustrated in Figure 4-60. (The contents and layout
of each BESTCOMSPlus programmable sender screen is identical; only the coolant temperature sender
screen is illustrated here.)

4-64

DGC-2020 BESTCOMSPlus Software

9400200990 Rev K