Figure 4-22. Engine Crank Settings

A

Cranking Style: Cycle or Continuous.

B

Number of Crank Cycles: Adjustable from 1 to 7 cycles in 1 cycle increments. Controllers configured for

NFPA compliance have a 1 to 3-cycle range.

C

Cycle Crank Time: Adjustable over the range of 5 to 15 seconds in 1 second increments.

D

Continuous Crank Time: Adjustable from 5 to 60 seconds in 1 second increments. Controllers

configured for NFPA compliance have a 1 to 45 second range.

E

Crank Disconnect Limit: Adjustable from 10 to 100% of nominal engine speed.

F

Pre-Crank Delay: Adjustable from 0 to 30 seconds in 1 second increments.

G

Pre-Start Contact Configuration: Open After Disconnect or Closed While Running.

H

Prestart Rest Configuration: Off During Rest, On During Rest, or Preheat Before Crank.

I

Oil Pressure Crank Disconnect Enable: Disable or Enable.

J

Crank Disconnect Pressure (psi): Adjustable from 3 to 150 psi in increments of 1 psi.

Automatic Restart
If the DGC-2020 has shut down due to an alarm condition, the automatic restart, when enabled

A

, will

automatically clear alarms. An attempt to restart the engine is made after a predetermined time delay

B

if

the ATS contact input is closed. If an ATS contact is not present, the unit will remain in READY state with
its alarms cleared. A restart will not be attempted if a low fuel alarm or emergency stop is present. The
number of restart attempts

C

is programmable. Automatic restart attempts are recorded in the event log.

BESTCOMSPlus automatic restart settings (DGC-2020, System Parameters, Automatic Restart) are
illustrated in Figure 4-23.

Figure 4-23. Automatic Restart Settings

A

Auto Restart Enable: Enable or Disable.

B

Auto Restart Interval:

Adjustable from 0.5 to 30 minutes in 0.5 minute increments.

C

Auto Restart Attempts: Adjustable from 1 to 10 in increments of 1.