Alarms, High coolant temp alarm enable, High coolant temp alarm threshold – Winco DGC-2020 User Manual

Page 309: Metric high coolant temp alarm threshold, High coolant temp alarm activation delay, Low oil press. alarm enable, Low oil press. alarm threshold, Metric low oil press. alarm threshold, Low oil press. alarm arming delay

Advertising
background image

9400200990 Rev K

DGC-2020 Modbus

Communication

B-33

Register Description Type

Units

Scaling

Factor

R/W Range

44396

3 Phase Reverse Power Alarm
Configuration

Uint32 N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

44398

3 Phase Reverse Power
Hysteresis

Int32

DeciPercent Deci

RW

10 - 100

44400

1 Phase Reverse Power Pickup

Uint32 DeciPercent Deci

RW (-500)

-

50

44402

1 Phase Reverse Power
Activation Delay

Uint32 Decisecond

Deci

RW

0 - 300

44404

1 Phase Reverse Power Alarm
Configuration

Uint32 N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

44406

1 Phase Reverse Power
Hysteresis

Int32

DeciPercent Deci

RW

10 - 100

44408

3 Phase Loss of Excitation
Pickup

Uint32 DeciPercent Deci

RW (-1500)

-

0

44410

3 Phase Loss of Excitation
Activation Delay

Uint32 Decisecond

Deci

RW

0 - 300

44412

3 Phase Loss of Excitation
Alarm Configuration

Uint32 N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

44414

3 Phase Loss of Excitation
Hysteresis

Int32

DeciPercent Deci

RW

10 - 100

44416

1 Phase Loss of Excitation
Pickup

Uint32 DeciPercent Deci

RW (-1500)

-

0

44418

1 Phase Loss of Excitation
Activation Delay

Uint32 Decisecond

Deci

RW

0 - 300

44420

1 Phase Loss of Excitation
Alarm Configuration

Uint32 N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

44422

1 Phase Loss of Excitation
Hysteresis

Int32

DeciPercent Deci

RW

10 - 100

44424

3 Phase Overcurrent Reset
Type (51-1)

Int32

N/A

N/A

RW

0 = Instantaneous
1 = Integrating

44426

1 Phase Overcurrent Reset
Type (51-1)

Int32

N/A

N/A

RW

0 = Instantaneous
1 = Integrating

44428

3 Phase Overcurrent Reset
Type (51-2)

Int32

N/A

N/A

RW

0 = Instantaneous
1 = Integrating

44430

1 Phase Overcurrent Reset
Type (51-2)

Int32

N/A

N/A

RW

0 = Instantaneous
1 = Integrating

44432-498 FUTURE

USE

Alarms

Register Description Type

Units

Scaling

Factor

R/W

Range

44500

High Coolant Temp Alarm
Enable

Uint32 N/A

N/A

RW

0 = Disable
1 = Enable

44502

High Coolant Temp Alarm
Threshold

Uint32 Deg F

N/A

RW

100 - 280

44504

Metric High Coolant Temp Alarm
Threshold

Int32

Deg C

N/A

RW

38 - 138

44506

High Coolant Temp Alarm
Activation Delay

Uint32 Second

N/A

RW

0 - 150

44508

Low Oil Press. Alarm Enable

Uint32 N/A

N/A

RW

0 = Disable
1 = Enable

44510

Low Oil Press. Alarm Threshold

Uint32 PSI

N/A

RW

3 - 150

44512

Metric Low Oil Press. Alarm
Threshold

Int32

Kpa

N/A

RW

21 - 1034

44514

Low Oil Press. Alarm Arming
Delay

Uint32 Second

N/A

RW

5 - 15