Remote LSM Inputs
When an optional LSM-2020 (Load Share Module) is connected, the value of the analog inputs is
displayed on this screen. Voltage is displayed when the input is configured for voltage and current is
displayed when the input is configured for current. Refer to Figure 4-74.

Figure 4-74. Metering, Inputs, Remote LSM Inputs

Remote Contact Inputs
When an optional CEM-2020 (Contact Expansion Module) is connected, the status of the remote contact
inputs, configurable remote contact input alarms, and remote contact input pre-alarms are shown on this
screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-75.

Figure 4-75. Metering, Inputs, Remote Contact Inputs

Remote Analog Inputs
When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote analog
inputs, remote analog input alarms, and remote analog input pre-alarms are shown on this screen. The
status is TRUE when the corresponding LED is red. Refer to Figure 4-76. Remote Analog Input #1 is
shown.

Figure 4-76. Metering, Inputs, Remote Analog Inputs

9400200990 Rev K

DGC-2020 BESTCOMSPlus Software