Figure 4-28. Remote LSM InputsSettings

A

Input Type: Voltage or Current.

B

Min/Max Input Voltage: Adjustable from 0 to 10 volts in 0.1 V increments.

C

Min/Max Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments.

Remote Contact Inputs
An optional CEM-2020 (Contact Expansion Module) provides 10 contact inputs. Each of the 10 contact
inputs can be independently configured to annunciate an alarm or pre-alarm

A

when the input senses a

contact closure. A user-adjustable time delay

B

can be set to delay recognition of a contact input. By

default, all inputs are configured so that they do not trigger an alarm or pre-alarm.
To make identifying the contact inputs easier, a user-assigned name

C

can be given to each input.

Contacts can be recognized

D

always or only while the engine is running.

Remote contact input status is available in BESTlogic+ Programmable Logic when “None” is selected for
Alarm Configuration.
BESTCOMSPlus settings for remote contact inputs (DGC-2020, Programmable Inputs, Remote Contact
Inputs) are illustrated in Figure 4-29.

Figure 4-29. Remote Contact Inputs Settings

A

Alarm Configuration: None, Alarm, or Pre-Alarm.

B

Activation Delay: Adjustable from 0 to 300 s in 1 s increments.

C

Label Text: An alphanumeric character string with a maximum of 16 characters.

D

Contact Recognition: Always or While Engine Running Only.

Remote Analog Inputs
An optional AEM-2020 (Analog Expansion Module) provides eight analog inputs. To make identifying the
analog inputs easier, a user-assigned name

A

can be given to each input.

9400200990 Rev K

DGC-2020 BESTCOMSPlus Software

4-31