1.18 aac for 1a cts, 7.75 aac for 5a cts, 9.9 for 40607=0-15 (inverse) – Winco DGC-2020 User Manual

Page 296: 30.0s for 40607=16 (fixed), 15 for inverse, 16 for fixed, 0=none, 1=pre-alarm, 2=alarm, Volts ac, 30.0 seconds, Hertz, 55.0 hz for 50-hz config

Advertising
background image

B-20 DGC-2020

Modbus

Communication

9400200990 Rev K

Holding

Register

Parameter Range

Read/Write

Supported

Data

Format

Units

40509-604 RESERVED

OVERCURRENT

40605

51 Pick-up – 3-phase

18-118,
90-775

R W

0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs

40606

51 Time Dial – 3-phase

0-99,
0-300

R W

0.0-9.9 for 40607=0-15 (inverse),
0.0-30.0s for 40607=16 (fixed)

40607

51 Curve – 3-phase

0-16

R W

0-15 for inverse, 16 for fixed

40608

51 Alarm Config. – 3-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

40609

51 Pick-up – 1-phase

18-118,
90-775

R W

0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs

40610

51 Time Dial – 1-phase

0-99,
0-300

R W

0.0-9.9 for 40607=0-15 (inverse),
0.0-30.0s for 40607=16 (fixed)

40611

51 Curve – 1-phase

0-16

R W

0-15 for inverse, 16 for fixed

40612

51 Alarm Config. – 1-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

PHASE IMBALANCE

40613

47 Pick-up

5-100

R W

Volts AC

40614

47 Time Delay

0-300

R W

0.0-30.0 seconds

40615

47 Alarm Configuration

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

UNDERVOLTAGE

40616

27 Pick-up – 3-phase

70-576

R W

Volts AC

40617

27 Time Delay – 3-phase

0-300

R W

0.0-30.0 seconds

40618

27 Inhibit Frequency- 3-ph.

20-400

R W

Hertz

40619

27 Alarm Config. – 3-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

40620

27 Pick-up – 1-phase

70-576

R W

Volts AC

40621

27 Time Delay – 1-phase

0-300

R W

0.0-30.0 seconds

40622

27 Inhibit Frequency – 1-ph.

20-400

R W

Hertz

40623

27 Alarm Config. – 1-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

OVERVOLTAGE

40624

59 Pick-up – 3-phase

70-576

R W

Volts AC

40625

59 Time Delay – 3-phase

0-300

R W

0.0-30.0 seconds

40626

59 Alarm Config. – 3-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

40627

59 Pick-up – 1-phase

70-576

R W

Volts AC

40628

59 Time Delay – 1-phase

0-300

R W

0.0-30.0 seconds

40629

59 Alarm Config. – 1-phase

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

UNDERFREQUENCY

40630 81U

Pick-up

450-550,
550-650,
3600-4400

R W

45.0-55.0 Hz for 50-Hz config.,
55.0-65.0 Hz for 60-Hz config.,
360.0-440.0 Hz for 400-Hz unit

40631

81U Time Delay

0-300

R W

0.0-30.0 seconds

40632

81U Inhibit Voltage

70-576

R W

Volts AC

40633

81U Alarm Configuration

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

OVERFREQUENCY

40634 81O

Pick-up

450-550,
550-650,
3600-4400

R W

45.0-55.0 Hz for 50-Hz config.,
55.0-65.0 Hz for 60-Hz config.,
360.0-440.0 Hz for 400-Hz unit

40635

81O Time Delay

0-300

R W

0.0-30.0 seconds

40636

81O Alarm Configuration

0-2

R W

0=None, 1=Pre-Alarm, 2=Alarm

GENERATOR PROTECTION STATUS

40637

Gen Protection Status (upper 16
bits)

0-65535 R b16-b31 UNASSIGNED

40638

Gen Protection Status (lower 16
bits)

0-65535 R

b0 = overvoltage trip,
b1 = undervoltage trip,
b2 = overfrequency trip,
b3 = underfrequency trip,
b4 = overcurrent trip,
b5 = phase imbalance trip,
b6-b15 UNASSIGNED

40639

Gen Protection Pre-Alarms (upper
16 bits)

0-65535 R b16-b31 UNASSIGNED