Table 10-2. Input and Output Terminals

Connector Description

P1

Operating Power and CANbus

P2

RTD Inputs 1 - 8

P3

Analog Inputs 1 - 8 and Analog Outputs 1 - 4

P4

Thermocouple 1 Input

P5

Thermocouple 2 Input

External RTD Input Connections

External 2-wire RTD input connections are shown in Figure 10-3. Figure 10-4 shows external 3-wire RTD
input connections.

RTD1+

RTD1–

RTD1C

AEM-2020

Jumper

P

00

5

3-

64

BLACK

RED

Figure 10-3. External Two-Wire RTD Input Connections

RTD1+

RTD1–

RTD1C

AEM-2020

P

00

5

3-

65

RED

BLACK

BLACK

Figure 10-4. External Three-Wire RTD Input Connections

CANbus Interface

These terminals provide communication using the SAE J1939 protocol and provide high-speed
communication between the Analog Expansion Module and the DGC-2020. Connections between the
AEM-2020 and DGC-2020 should be made with twisted-pair, shielded cable. CANbus interface terminals
are listed in Table 10-3. Refer to Figure 10-5 and Figure 10-6.

10-6