OEM Access. This password level allows access to all settings. The default, OEM-access password

is OEM.

Settings Access. This password level allows all except uploading of firmware and clearing of device

event log. The default, settings-access password is SET.

Operator Access. The default, operator-access password is OP. This password level allows all

settings to be read and allows changes to be made to the following:

o

LCD

Contrast

o

Sleep

Mode

o

Date/Time

o

All Sender Fail Time Delays

o

Metric

Conversion

o

Low Fuel Pre-Alarm Level

o

Low Fuel Alarm Level

o

Pre-Start Contact after Cranking

o

Cooldown

Time

o

Pre-Crank Time Delay

o

Reset of Maintenance Interval

o

All controls on the Control screen available via the Metering Explorer in BESTCOMSPlus

Changing Passwords
Passwords can be changed only after communication between the PC and DGC-2020 is established.
Changes to passwords are made through the Device Security Setup screen. Use the Settings Explorer in
BESTCOMSPlus to open the General Settings, Device Security Setup screen.
The content of the Device Security Setup screen depends on the password level used when accessing
the screen. For example, someone logged in with a settings-access password will be able to change only
the settings-access and operator-access passwords - not the OEM-access password. Figure 4-14
illustrates the Device Security Setup screen with all three of the access levels shown.
A password is changed by clicking on the access level

A

, entering the new password

B

, and then clicking on

the Save Password button

C

.

Figure 4-14. Device Security Setup

A

Access Level/Password: Read-only value obtained when BESTCOMSPlus is communicating with the

DGC-2020.

B

Password: Accepts an alphanumeric character string of up to 16 characters.

C

Save Password: Clicking this button will save the password changes in BESTCOMSPlus memory.

Clock Setup
Configuration of daylight saving time and coordination of the local time with universal time (if desired) is
performed on this screen. If required, enter the UTC (Universal Time Coordinates) Offset

A

. Choose the

type of DST Configuration

B

and then set the Start Day

C

, End Day

D

,

and Bias

E

.

See Figure 4-15.