Senders, Coolant temperature sender fail configuration type, Coolant temperature sender fail activation delay – Winco DGC-2020 User Manual

Page 301: Oil pressure sender fail configuration type, Oil pressure sender fail activation delay, Fuel level sender fail configuration type, Fuel level sender fail activation delay, Voltage sensing fail configuration type, Voltage sensing fail activation delay, Future use

Advertising
background image

9400200990 Rev K

DGC-2020 Modbus

Communication

B-25

Register Description

Type

Units

Scaling

Factor

R/W

Range

42768

Gen Sensing Stable Overfrequency Pickup

Int32

CentiHertz

Centi

RW

4600 - 6400

42770

Gen Sensing Stable Overfrequency Dropout

Int32

CentiHertz

Centi

RW

4600 - 6400

42772

Gen Sensing Fail Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42774

Gen Sensing Stable Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42776 RESERVED

42778

Bus Sensing Dead Bus Pickup

Int32

Volt

N/A

RW

1 - 4800

42780

Bus Sensing Dead Bus Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42782 RESERVED

42784

Bus Sensing Stable Undervoltage Pickup

Int32

Volt

N/A

RW

10 - 9999

42786

Bus Sensing Stable Undervoltage Dropout

Int32

Volt

N/A

RW

10 - 9999

42788

Bus Sensing Stable Overvoltage Pickup

Int32

Volt

N/A

RW

10 - 9999

42790

Bus Sensing Stable Overvoltage Dropout

Int32

Volt

N/A

RW

10 - 9999

42792

Bus Sensing Stable Underfrequency Pickup

Int32

CentiHertz

Centi

RW

4600 - 6400

42794

Bus Sensing Stable Underfrequency Dropout

Int32

CentiHertz

Centi

RW

4600 - 6400

42796

Bus Sensing Stable Overfrequency Pickup

Int32

CentiHertz

Centi

RW

4600 - 6400

42798

Bus Sensing Stable Overfrequency Dropout

Int32

CentiHertz

Centi

RW

4600 - 6400

42800

Bus Sensing Fail Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42802

Bus Sensing Stable Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42804 RESERVED

42806

Gen Dead Status

Int32

N/A

N/A

R

0 - 1

42808

Gen Stable Status

Int32

N/A

N/A

R

0 - 1

42810

Gen Fail Status

Int32

N/A

N/A

R

0 - 1

42812

Bus Dead Status

Int32

N/A

N/A

R

0 - 1

42814

Bus Stable Status

Int32

N/A

N/A

R

0 - 1

42816

Bus Fail Status

Int32

N/A

N/A

R

0 - 1

42818

Gen Stable Low Line Scale Factor

Float

N/A

N/A

RW

0 - 3

42820

Bus Stable Low Line Scale Factor

Float

N/A

N/A

RW

0 - 3

42822-3432 FUTURE

USE

Senders

Register Description

Type

Units

Scaling

Factor

R/W Range

43434

Coolant Temperature Sender Fail Configuration
Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

43436

Coolant Temperature Sender Fail Activation Delay

Int32

Minute

N/A

RW

5 - 30

43438

Oil Pressure Sender Fail Configuration Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

43440

Oil Pressure Sender Fail Activation Delay

Int32

Second N/A

RW

0 - 300

43442

Fuel Level Sender Fail Configuration Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

43444

Fuel Level Sender Fail Activation Delay

Int32

Second N/A

RW

0 - 300

43446

Voltage Sensing Fail Configuration Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

43448

Voltage Sensing Fail Activation Delay

Int32

Second N/A

RW

0 - 300

43450-498

FUTURE USE

Int32

N/A

RW

System Configuration and Status

Register Description Type

Units

Scaling

Factor

R/W Range

43500

Rated Volts

Float

Volt

N/A

RW

1 - 99999

Advertising