Run mode, Off or auto mode (not running), Auto mode (running) – Winco DGC-2020 User Manual

Page 59: Breaker operation, Determining if it is acceptable to close a breaker, Changing the breaker state, Synchronizer operation, Run mode -11, Off or auto mode (not running) -11, Auto mode (running) -11

Advertising
background image

9400200990 Rev K

DGC-2020 Functional Description

3-11

The type of response given for a local request depends on the operating mode of the DGC-2020.

RUN Mode

When in RUN mode, the generator and mains breakers can be closed manually using contact inputs or
the breaker buttons on the BESTCOMSPlus Control screen.

OFF or AUTO Mode (Not Running)

If operating in the OFF mode or AUTO and not running, the generator breaker cannot be closed because
the generator will not be stable.

AUTO Mode (Running)

When in AUTO mode and running, the mains fail transfer feature will automatically control the mains
breaker and the generator breaker or the external ATS (automatic transfer switch) will start the generator
and control the breakers itself. In addition, the generator breaker can be automatically controlled by the
demand start/stop function, the exercise timer function, or a RUNWLOAD (run with load) start from the
PLC. The generator breaker can be manually controlled using contact inputs and outputs or the breaker
buttons on the BESTCOMSPlus Control screen.

Breaker Operation

The DGC-2020 will attempt to close a breaker only after verifying that it can be closed. If the breaker
cannot be closed, the close request will be ignored. Only one breaker can be closed at a time.
Synchronization is required before closing the breaker to a live bus. Closure to a dead bus can be
performed after meeting dead bus threshold and timing requirements set by the user.

Determining if it is Acceptable to Close a Breaker

Before the generator breaker can be closed, it must be configured in BESTCOMSPlus. If only the
generator breaker is configured (mains breaker not configured) the DGC-2020 looks at user settings to
determine if the generator side of the breaker is stable and the bus side is stable or dead. If both the
generator and the mains breakers are configured and open, the DGC-2020 will close the generator
breaker if the generator side of the breaker is stable. If both breakers are configured and the mains
breaker is closed, the DGC-2020 will close the generator breaker after verifying that both sides of the
generator breaker are stable and the DGC-2020 is synchronizing.

Before the mains breaker can be closed, it must be configured in BESTCOMSPlus. If both the mains and
the generator breakers are configured and open, the DGC-2020 will close the mains breaker if the mains
side of the breaker is stable. If both breakers are configured and the generator breaker is closed, the
DGC-2020 will close the mains breaker after verifying that both sides of the mains breaker are stable.

Changing the Breaker State

Synchronization is required when closing a breaker to a live bus. Bus conditions act as a supervisory
control over the synchronizing function. If synchronization is in process and either bus goes unstable,
synchronization is suspended. To close the breaker on a dead bus, the DGC-2020 generates a breaker
close request. The closing function is then run without synchronization.

The GENBRK and MAINSBRK logic blocks contain both Open and Close logic outputs that can be
configured to energize an output contact, which would in turn operate the breaker. The Synchronizer
screen in BESTCOMSPlus is used to set the output contact type to pulses or continuous.

If the breaker does not seem to operate properly, refer to Section 7, Maintenance and Troubleshooting.

Synchronizer Operation

The synchronizer acts to align the generator voltage and frequency with that of the bus inputs when the
DGC-2020 desires to close the generator to a live, stable bus. Several situations must exist before the
synchronizer function will begin to execute:

 The DGC-2020 must include the synchronizer option
 The generator voltage must be stable
 The bus voltage must be stable
 The DGC-2020 must be in the process of initiating a breaker close