Contact sensing, Terminals, Engine system inputs – Winco DGC-2020 User Manual

Page 17: Fuel level sensing, Coolant temperature sensing, Oil pressure sensing, Engine speed sensing, Output contacts, Fuel solenoid, engine crank, and pre-start relays, Contact sensing -5

Advertising
background image

9400200990 Rev K

DGC-2020 General Information

1-5

Contact Sensing
Contact sensing inputs include 1 emergency stop input and 16 programmable inputs. The emergency
stop input accepts normally closed, dry contacts. All programmable inputs accept normally open, dry
contacts.

Terminals
Emergency Stop:

46, 47

Programmable

Input 1:

30, 2

Input 2:

29, 2

Input 3:

28, 2

Input 4:

27, 2

Input 5:

26, 2

Input 6:

25, 2

Input 7:

24, 2

Input 8:

23, 2

Input 9:

22, 2

Input 10:

21, 2

Input 11:

20, 2

Input 12:

19, 2

Input 13:

18, 2

Input 14:

17, 2

Input 15:

16, 2

Input 16:

15, 2

Engine System Inputs
 Stated accuracies are subject to the accuracy of the senders used.

Fuel Level Sensing
Resistance Range:

33 to 240 Ω nominal

Terminals:

9, 11 (sender common)

Coolant Temperature Sensing
Resistance Range:

62.6 to 637.5 Ω nominal

Terminals:

10, 11 (sender common)

Oil Pressure Sensing
Resistance Range:

34 to 240 Ω nominal

Terminals:

8, 11 (sender common)

Engine Speed Sensing
Magnetic Pickup

Voltage Range:

3 to 35 V peak (6 to 70 V peak-peak)

Frequency Range:

32 to 10,000 Hz

Terminals:

31 (+), 32 (–)

Generator Voltage

Range:

12 to 576 V rms

Terminals:

41

(A-phase)

39

(B-phase)

37

(C-phase)

Output Contacts

Fuel Solenoid, Engine Crank, and Pre-Start Relays
Rating: 30 Adc at 28 Vdc—make, break, and carry

Terminals

Fuel Solenoid:

RUN – NO, COM

Pre-Start:

PRE – NO, COM

Crank:

START – NO, COM

Advertising