Bus Transformer Settings
Primary and secondary bus transformer ratings are used by the automatic transfer switch function, which
monitors a single-phase bus input to detect mains failure. Controllers equipped with an automatic
synchronizer (style number xxxxxxxAx) also use the primary and secondary bus transformer ratings. The
primary setting

D

establishes the nominal voltage present at phases A and C of the bus. The secondary

setting

E

establishes the nominal voltage seen at the bus voltage input of the DGC-2020.

BESTCOMSPlus sensing transformer settings (DGC-2020, System Parameters, Sensing Transformers)
are illustrated in Figure 4-25.

Figure 4-25. Sensing Transformers Parameters

A

Gen PT Primary Volts: Adjustable from 1 to 9999 Vac in 1 Vac increments.

B

Gen PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments.

C

Gen CT Primary Amps: Adjustable from 1 to 5,000 Aac in 1 Aac increments.

D

Bus PT Primary Volts: Adjustable from 1 to 9999 Vac in 1 Vac increments.

E

Bus PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments.

PROGRAMMABLE INPUTS

DGC-2020 programmable inputs can be assigned to trigger various functions and, when triggered,
annunciate an alarm or pre-alarm. A user-assigned label can be assigned to each input to make
identification easier. The description of these settings is organized as follows:
 Contact

Inputs

 Programmable

Functions

 Remote LSM Inputs (Available with an optional LSM-2020 (Load Share Module).

 Remote Contact Inputs (Available with an optional CEM-2020 (Contact Expansion Module).

 Remote Analog Inputs (Available with an optional AEM-2020 (Analog Expansion Module).

 Remote RTD Inputs (Available with an optional AEM-2020 (Analog Expansion Module).

 Remote Thermocouple Inputs (Available with an optional AEM-2020 (Analog Expansion Module).

Contact Inputs
Each of the 16 contact inputs can be independently configured to annunciate an alarm or pre-alarm

A

when the input senses a contact closure. A user-adjustable time delay

B

can be set to delay recognition of

a contact input. By default, all inputs are configured so that they do not trigger an alarm or pre-alarm.
To make identifying the contact inputs easier, a user-assigned name

C

can be given to each input.

Contacts can be recognized

D

always or while the engine is running only.

Contact input status is available in BESTlogic+ Programmable Logic when “None” is selected for Alarm
Configuration.
BESTCOMSPlus settings for contact inputs (DGC-2020, Programmable Inputs, Contact Inputs) are
illustrated in Figure 4-26.

4-28

DGC-2020 BESTCOMSPlus Software