Remote analog outputs, Remote analog outputs -36, Figure 4-35. remote contact outputs settings -36 – Winco DGC-2020 User Manual

Page 106: Figure 4-36. remote analog outputs settings -36

Advertising
background image

BESTCOMSPlus settings for remote contact inputs (DGC-2020, Programmable Outputs, Remote Contact
Outputs) are illustrated in Figure 4-35.

Figure 4-35. Remote Contact Outputs Settings

A

Label Text: An alphanumeric character string with a maximum of 16 characters.

Remote Analog Outputs
An optional AEM-2020 (Analog Expansion Module) provides four analog outputs.
Make a parameter selection

A

and select the output type

B

. When enabled, an out of range alarm

C

alerts

the user of an open or damaged analog output wire. An out of range activation delay

D

setting delays

alarm annunciation.
Ranges must be set for the selected output type. Param Min

E

correlates to Min Input Current

F

or Min Input

Voltage

G

and Param Max

H

correlates to Max Input Current

I

or Max Input Voltage

J

.

A remote analog output is disabled when Alarm Configuration is set to “None”. Remote analog output
status is available in BESTlogic+ Programmable Logic when “Status Only” is selected.
BESTCOMSPlus settings for remote analog outputs (DGC-2020, Programmable Inputs, Remote Analog
Outputs) are illustrated in Figure 4-36. Remote Analog Output #1 is shown.

Figure 4-36. Remote Analog Outputs Settings

A

Param Selection: Oil Pressure, Battery Temp, Coolant Volts, RPM, Fuel Level, Gen VAB, Gen VBC,

Gen VCA, Gen VAN, Gen VBN, Gen VCN, Bus Freq, Bus Volts, Gen Freq, Gen PF, Gen IA, Gen IB, Gen
IC, KW A, KW B, KW C, KW Total, Analog Input 1-8, RTD Input 1-8, or Thermocouple Input 1-2.

B

Output Type: Voltage or Current.

C

Out of Range Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only.

4-36

DGC-2020 BESTCOMSPlus Software

9400200990 Rev K

D

Out of Range Activation Delay: Adjustable from 0 to 300 s in 1 s increments.