Rs-485 (optional), Modem (optional), Output contacts – Winco DGC-2020 User Manual

Page 56: Rs-485 (optional) -8, Modem (optional) -8, Output contacts -8

Advertising
background image

3-8

DGC-2020 Functional Description

9400200990 Rev K

265, SD BANK 2 TEST
266, SD SPD DEMAND AN
267, SD SPDMTEST BNCH
269, SD LOAD PLS ANLG
270, SD SPD DEMAND
271, SD T-EXTERN 1
272, SD T-EXTERN 2
273, SD P-EXTERN 1
274, SD P-EXTERN 2
275, MD EXT.CLNT LVL
276, MD INTERCLER LVL
277, MISDATA BIN-EXT3
278, MISDATA BIN-EXT4
279, SD CANRES TRIPFL
280, SD CAN ALRM RST
281, SD ADTEST1 SPPLY
282, SD ADTEST2 SPPLY
283, SD ADTEST3 SPPLY
284, SD CAN LAMP TEST
301, TIMING CYLNDR A1
302, TIMING CYLNDR A2
303, TIMING CYLNDR A3
304, TIMING CYLNDR A4
305, TIMING CYLNDR A5
306, TIMING CYLNDR A6
307, TIMING CYLNDR A7
308, TIMING CYLNDR A8
309, TIMING CYLNDR A9
310, TIMING CYLNDR A10
311, TIMING CYLNDR B1
312, TIMING CYLNDR B2
313, TIMING CYLNDR B3
314, TIMING CYLNDR B4
315, TIMING CYLNDR B5
316, TIMING CYLNDR B6
317, TIMING CYLNDR B7
318, TIMING CYLNDR B8
319, TIMING CYLNDR B9
320, TIMING CYLNDR B10
321, WIRING CYLNDR A1
322, WIRING CYLNDR A2

323, WIRING CYLNDR A3
324, WIRING CYLNDR A4
325, WIRING CYLNDR A5
326, WIRING CYLNDR A6
327, WIRING CYLNDR A7
328, WIRING CYLNDR A8
329, WIRING CYLNDR A9
330, WIRING CYLNDR A10
331, WIRING CYLNDR B1
332, WIRING CYLNDR B2
333, WIRING CYLNDR B3
334, WIRING CYLNDR B4
335, WIRING CYLNDR B5
336, WIRING CYLNDR B6
337, WIRING CYLNDR B7
338, WIRING CYLNDR B8
339, WIRING CYLNDR B9
340, WIRING CYLNDR B10
341, OPN LD CYLNDR A1
342, OPN LD CYLNDR A2
343, OPN LD CYLNDR A3
344, OPN LD CYLNDR A4
345, OPN LD CYLNDR A5
346, OPN LD CYLNDR A6
347, OPN LD CYLNDR A7
348, OPN LD CYLNDR A8
349, OPN LD CYLNDR A9
350, OPN LD CYLNDR A10
351, OPN LD CYLNDR B1
352, OPN LD CYLNDR B2
353, OPN LD CYLNDR B3
354, OPN LD CYLNDR B4
355, OPN LD CYLNDR B5
356, OPN LD CYLNDR B6
357, OPN LD CYLNDR B7
358, OPN LD CYLNDR B8
359, OPN LD CYLNDR B9
360, OPN LD CYLNDR B10
361, PWR STG FL 1
362, PWR STG FL 2
363, STP PWR STG 1

364, STP PWR STG 2
365, STOP MV-WIRING
381, TRAN OUT1 PLNT DEF
382, TRAN OUT2 PLNT DEF
383, TRAN OUT3 PLNT DEF
384, TRAN OUT4 PLNT DEF
385, TRAN OUT5 PLNT DEF
386, TRAN OUT6 PLNT DEF
390, AL MCR EXCEEDED
399, INTERFACE ECU
400, AL OPN LD DIGIN 1
401, AL OPN LD DIGIN 2
402, AL OPN LD DIGIN 3
403, AL OPN LD DIGIN 4
404, AL OPN LD DIGIN 5
405, AL OPN LD DIGIN 6
406, AL OPN LD DIGIN 7
407, AL OPN LD DIGIN 8
408, AL OPN LD DIGIN 9
410, LO U-PDU
411, LOLO U-PDU
412, HI U-PDU
413, HIHI U-PDU
434, SD P-AUX 1
444, SL U-PDU
450, SD IDLE-END TRQ
454, SS PWR RED ACT
468, SD T-AUX 1
469, SD AUX 1
470, SD T-ECU
471, SD COIL CURRENT
472, AL STOP SD
474, AL WIRING FO
475, AL CR TRIG ENG ST
476, AL CR INIT ERR
478, AL COMB ALM YEL
479, AL COMB ALM RED
480, AL EXT ENG PROT
555, AL CALL MTU FS

RS-485 (Optional)

DGC-2020 controllers with the optional RS-485 communication port (style number xxxRxxxxx) can be
monitored and controlled via a polled network using the Modbus

®

protocol. The RS-485 port supports a

user-selectable baud rate of 1200, 2400, 4800, or 9600. Odd, even, or no parity is supported. Fixed
communication settings include the number of data bits (8) and stop bits (1). Modbus register values for
the DGC-2020 are listed and defined in Appendix B, Modbus Communication. RS-485 port connections
are made at DGC-2020 terminals 14 (485A), 13 (485B), and 12 (485 SHIELD).

Modem (Optional)

When equipped with the optional, internal, dial-out modem, the DGC-2020 can be connected to a
standard telephone line through its RJ-11 jack. The modem enables the DGC-2020 to dial up to four
pager telephone numbers and annunciate conditions selected by the user. These conditions include any
DGC-2020 alarm or pre-alarm, closure of any programmable contact input, and an active cooldown timer.
The modem accommodates pagers that use seven data bits with even parity or modems using eight data
bits with no parity.

Output Contacts

Output contact operation is controlled by the operating mode of the DGC-2020. The state of the
Emergency Stop contact input also affects output contact operation. When the Emergency Stop contact

Advertising