Apparent power, Power factor, Real power – Winco DGC-2020 User Manual

Page 19: Oil pressure, Coolant temperature, Battery voltage, Engine rpm, Engine run time, Apparent power -7, Power factor -7

Advertising
background image

9400200990 Rev K

DGC-2020 General Information

1-7

Apparent Power
Indicates total kVA and individual line kVA (4-wire, line-to-neutral or 3-wire, line-to-line).
Measurement/Calculation Methods

Total:

kVA = (V

L-L

 I

L

3) ÷ 1000

4-Wire, Line-to-Neutral:

kVA calculated with respect to neutral

3-Wire, Line-to-Line:

A-phase kVA = V

AB

 I

A

 1000  3

B-phase

kVA

=

V

BC

 I

B

 1000  3

C-phase kVA = V

CA

 I

C

 1000  3

Accuracy:

3% or the full-scale indication or 2 kVA †

 kVA metering indicates 0 kVA when the generator kVA is below 2% of the full-scale rating.
† Applies when temperature is between -40

C to +70C.

Power Factor
Metering Range:

0.2 leading to 0.2 lagging

Calculation Method:

PF = P (3-phase average)

 S (3-phase average)

Accuracy:

0.02 

 Applies when temperature is between –40C to +70C.

Real Power
Indicates total kW and individual line kW (4-wire, line-to-neutral or 3-wire line-to-line)
Measurement/Calculation Methods
Total:

PF

 Total kVA

4-Wire, Line-to-Neutral:

kW calculated with respect to neutral

3-Wire, Line-to-Line:

A-phase kW = V

AB

 I

A

 PF  1000  3

B-phase

kW

=

V

BC

 I

B

 PF  1000  3

C-phase

kW

=

V

CA

 I

C

 PF  1000  3

Accuracy:

3% of the full-scale indication or 2 kW †

 kW metering indicates 0 kW when the generator kW is below 2% of the full-scale rating.
† Applies when temperature is between –40

C to +70C.

Oil Pressure
Metering Range:

0 to 145 psi or 0 to 1,000 kPa

Accuracy:

3% of actual indication or 2 psi or 12 kPa (subject to accuracy of
sender)

Display Resolution:

1 psi or 1 kPa

Coolant Temperature
Metering Range:

32 to 410

F or 0 to 204C

Accuracy:

3% of actual indication or 2 (subject to accuracy of sender)

Battery Voltage
Metering Range:

6 to 32 Vdc

Accuracy:

3% of actual indication or 0.2 Vdc

Display Resolution:

0.1 Vdc

Engine RPM
Metering Range:

0 to 4,500 rpm

Accuracy:

2% of actual indication or 2 rpm

Display Resolution:

2 rpm

 When engine speed is below 2% of full-scale, reported rpm is 0.

Engine Run Time
Engine run time is retained in nonvolatile memory.
Metering Range:

0 to 99,999 h

Update Interval:

6 min

Accuracy:

1% of actual indication or 12 min

Display Resolution:

1/10 hour