Connections with aem-2020, cem-2020, and lsm-2020, Installation for ce systems, Installation in a salt fog environment – Winco DGC-2020 User Manual

Page 210: Installation for ce systems -24, Installation in a salt fog environment -24, Lsm-2020, Cem-2020

Advertising
background image

Connections with AEM-2020, CEM-2020, and LSM-2020

The AEM-2020 (Analog Expansion Module), CEM-2020 (Contact Expansion Module), and LSM-2020
(Load Share Module) are optional modules that may be installed with the DGC-2020. These modules
interface to the DGC-2020 via CANbus, thus the CANBUS terminals are the only common connections
(Figure 6-18) between the DGC-2020, AEM-2020, CEM-2020, and LSM-2020. Refer to Section 8, LSM-
2020 (Load Share Module),
for independent LSM-2020 connections. Refer to Section 9, CEM-2020
(Contact Expansion Module),
for independent CEM-2020 connections. Refer to Section 10, AEM-2020
(Analog Expansion Module),
for independent AEM-2020 connections. Refer to Connections, CANbus
Interface,
in this section for details on DGC-2020 CANbus connections.

GND

CANH

CANL

LSM-2020

P0053-57

AEM-2020

DGC-2020

CANH

CANL

GND/SHIELD

CEM-2020

GND

CANH

CANL

GND

CANH

CANL

GND

CANH

CANL

Figure 6-18. DGC-2020, AEM-2020, CEM-2020, LSM-2020 CANbus Connections

INSTALLATION FOR CE SYSTEMS

For CE compliant systems, it may be required to route ac voltage and current sensing wires separately
from other wires.

INSTALLATION IN A SALT FOG ENVIRONMENT

If the DGC-2020 will be installed in a salt-fog environment, it is recommended that the backup battery for
the real-time clock be removed. Salt fog is known to be conductive and may short-circuit the battery.

Information on removing the backup battery for the real-time clock can be found in Section 7,
Maintenance and Troubleshooting.

6-24

DGC-2020 Installation

9400200990 Rev K