Type tests, Shock, Vibration – Winco DGC-2020 User Manual

Page 246: Ignition system, Halt (highly accelerated life testing), Environment, Ul approval, Nfpa compliance, Ce compliance, Physical

Advertising
background image

10-2

DGC-2020 AEM-2020 (Analog Expansion Module)

9400200990 Rev K

Type Tests

Shock

15 G in 3 perpendicular planes

Vibration

Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each
15-minute sweep consisting of the following:

5 to 29 to 5 Hz:

1.5 G peak for 5 min.

29 to 52 to 29 Hz:

0.036” Double Amplitude for 2.5 min.

52 to 500 to 52 Hz:

5 G peak for 7.5 min.

Ignition System

Tested in closed proximity to an unshielded, unsuppressed Altronic DISN 800 ignition system.

HALT (Highly Accelerated Life Testing)

HALT is used by Basler Electric to prove that our products will provide the user with many years of
reliable service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate
years of operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible
design elements that will add to the life of this device. As an example of some of the extreme testing
conditions, the AEM-2020 was subjected to temperature tests (tested over a temperature range of –80

C

to +130

C),

vibration tests (of 5 to 50 G at +25

C), and temperature/vibration tests (tested at 10 to 20 G

over a temperature range of –60

C to +100C). Combined temperature and vibration testing at these

extremes proves that the AEM-2020 is expected to provide long-term operation in a rugged environment.
Note that the vibration and temperature extremes listed in this paragraph are specific to HALT and do not
reflect recommended operation levels. These operational ratings are included in Section 10 of this
manual.

Environment

Temperature

Operating:

–40

to

+70

C (–40 to +158F)

Storage:

–40

to

+85

C (–40 to +185F)

Humidity:

IEC

68-2-38

UL Approval

“cURus” recognized to UL Standard 508 & CSA Standard C22.2 No.14

“cURus” recognized per Standard 1604, Electrical Equipment for Use in Class I and II, Division 2, and
Class III Hazardous (Classified) Locations,
Class I, Division 2, Zone 2, Groups A, B, C, D,
Temperature Code - T4.

NFPA Compliance

Complies with NFPA Standard 110, Standard for Emergency and Standby Power.

CE Compliance

This product complies with the requirements of the following EC Directives:

 Low Voltage Directive (LVD) - 73/23/EEC as amended by 93/68/EEC

 Electromagnetic Compatibility (EMC) - 89/336/EEC as amended by 92/31/EEC and 93/68/EEC

This product conforms to the following Harmonized Standards:

 EN 50178:1997 - Electronic Equipment for use in Power Installations

 EN 61000-6-4:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Emission Standard

for Industrial Environments

 EN 61000-6-2:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Immunity for

Industrial Environments

Physical

Weight:

1.80

lb

(816

g)

Dimensions:

See

Installation later in this section.

Advertising