Part numbers, Specifications, Operating power – Winco DGC-2020 User Manual

Page 16: Power consumption, Battery ride through, Current sensing, 1 aac current sensing, 5 aac current sensing, Voltage sensing, Part numbers -4

Advertising
background image

1-4

DGC-2020 General Information

9400200990 Rev K

Part Numbers
A ten-digit part number specifies the electrical characteristics and operational features of special-order
DGC-2020 controllers. Table 1-1 lists the special-order DGC-2020 controllers available along with
descriptions of their operating features.

Table 1-1. Special-Order DGC-2020 Controllers

Part Number

Style Number

Special Features

9400200105 51ANBNSNH001
9400200106 11ANBNSNH001

cURus recognized for use in
hazardous locations.

SPECIFICATIONS

Operating Power
Nominal:

12 or 24 Vdc

Range:

6 to 32 Vdc (Withstands cranking ride-through down to 6 Vdc
for 500 ms.)

Terminals:

3 (+), 2 (–), 1 (chassis ground)

Power Consumption
Sleep Mode:

5W with all relays non-energized

Normal Operational Mode:

7.9W - Run mode, LCD heater off, 3 relays energized

Maximum Operational Mode:

14.2W - Run mode, LCD heater on, 6 relays energized

Battery Ride Through
Withstands cranking ride-through down to 0 V for 50 ms.

Current Sensing
Burden:

1 VA

Terminals:

68, 69 (A-phase)

71,

72

(B-phase)

74,

75

(C-phase)

1 Aac Current Sensing
Continuous Rating:

0.02 to 1.0 Aac

1 Second Rating:

2 Aac

5 Aac Current Sensing
Continuous Rating:

0.1 to 5.0 Aac

1 Second Rating:

10 Aac

Voltage Sensing
Configuration:

Line-to-line or line-to-neutral

Range:

12 to 576 V rms, line-to-line

Frequency:

Style selectable, 50/60 Hz or 400 Hz

Frequency Range:

10 to 72 Hz for 50/60 style and 10 to 480 Hz for 400 Hz style

Burden:

1 VA

1 Second Rating:

720 V rms

Generator Sensing Terminals:

41 (A-phase)

39

(B-phase)

37

(C-phase)

35

(Neutral)

Bus Sensing Terminals:

45 (A-phase)

43

(B-phase)

Advertising