Maintenance interval pre-alarm enable, Maintenance interval pre-alarm threshold, Speed sender fail activation delay – Winco DGC-2020 User Manual

Page 311: Ecu low coolant level alarm enable, Ecu low coolant level alarm threshold, Ecu low coolant level pre-alarm enable, Ecu low coolant level pre-alarm threshold, Battery overvoltage alarm threshold, Engine overload 1 pre-alarm, 3 phase hysteresis

Advertising
background image

9400200990 Rev K

DGC-2020 Modbus

Communication

B-35

Register Description Type

Units

Scaling

Factor

R/W

Range

44578

Maintenance Interval Pre-Alarm
Enable

Uint32 N/A

N/A

RW

0 = Disable
1 = Enable

44580

Maintenance Interval Pre-Alarm
Threshold

Uint32 Hour

N/A

RW

0 - 5000

44582

Speed Sender Fail Activation
Delay

Int32

Second

N/A

RW

0 - 300

44584

ECU Low Coolant Level Alarm
Enable

Uint32 N/A

N/A

RW

0 = Disable
1 = Enable

44586

ECU Low Coolant Level Alarm
Threshold

Uint32 Percent

N/A

RW

1 - 99

44588

ECU Low Coolant Level Pre-
Alarm Enable

Uint32 N/A

N/A

RW

0 = Disable
1 = Enable

44590

ECU Low Coolant Level Pre-
Alarm Threshold

Uint32 Percent

N/A

RW

1 - 99

44592

Battery Overvoltage Alarm
Threshold

Int32

DeciVolt

Deci

RW

120 - 320

44594

Engine Overload 1 Pre-Alarm
3 Phase Hysteresis

Int32

DeciVolt

Deci

RW

1 - 10

44596

Engine Overload 1 Pre-Alarm
1 Phase Threshold

Int32

Percent

N/A

RW

95 - 140

44598

Engine Overload 1 Pre-Alarm
1 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

44600

Engine Overload 1 Pre-Alarm
1 Phase Low Line Scale Factor

Float

N/A

N/A

RW

0 - 3

44602

Engine Overload 2 Pre-Alarm
Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44604

Engine Overload 2 Pre-Alarm
3 Phase Threshold

Int32

Percent

N/A

RW

95 - 140

44606

Engine Overload 2 Pre-Alarm
3 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

44608

Engine Overload 2 Pre-Alarm
1 Phase Threshold

Int32

Percent

N/A

RW

95 - 140

44610

Engine Overload 2 Pre-Alarm
1 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

44612

Engine Overload 2 Pre-Alarm
1 Phase Low Line Scale Factor

Float

N/A

N/A

RW

0 - 3

44614

Engine Overload 3 Pre-Alarm
Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44616

Engine Overload 3 Pre-Alarm
3 Phase Threshold

Int32

Percent

N/A

RW

95 - 140

44618

Engine Overload 3 Pre-Alarm
3 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

44620

Engine Overload 3 Pre-Alarm
1 Phase Threshold

Int32

Percent

N/A

RW

95 - 140

44622

Engine Overload 3 Pre-Alarm
1 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

44624

Engine Overload 3 Pre-Alarm
1 Phase Low Line Scale Factor

Float

N/A

N/A

RW

0 - 3

44626

LSM Comm Failure Pre-alarm
Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44628

Intergenset Comm Failure Pre-
alarm Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44630

AVR Bias Output Limit Pre-
alarm Activation Delay

Int32

Second

N/A

RW

1 - 15

44632

AVR Bias Output Limit Pre-
alarm Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

Advertising