113

Speed

Return action

Returned position

250.34 mm

Target position

280 mm

Position where the push &
hold operation completed

290.34 mm

3.4.1

Return Action after Push & Hold by Relative Coordinate Specification

 Positioning mode

The reference position is the target position for the position number used in the applicable push & hold operation.
In the aforementioned example, the actuator moves to the 240-mm position if position No. 2 is set to -40 mm in
the incremental mode (280 – 40 = 240 mm).









 Push & hold mode

The reference position is the position where the push & hold operation completed.
In the aforementioned example, the actuator moves to the 250.34-mm position if position No. 2 is set to -40 mm
in the incremental mode and the push & hold operation completed at 290. 34 mm (290.34 – 40 = 250.34 mm).
(Note) In this case, the controller determines that the actuator has missed the load and thus does not turn ON

the position complete signal.
It is therefore recommended that the zone output signal be used to determine completion of push & hold
operation on the PLC side.








Caution: When the start signal turns ON, the position complete output will turn OFF and the moving output will

turn ON.
Always turn OFF the start signal after confirming that the start signal is currently ON and the position
complete output has turned OFF.
If the actuator has missed the load, the position complete output will not turn ON as shown below. The
completed position will be output and the moving output will turn OFF.










Speed

Return action

Returned position

240 mm

Position where the push &
hold operation completed

Target position

280 mm

Command position

Start

Position complete

Moving

Completed position

Actuator movement

Speed

Position 1

Position 2

Position 1

Position 1

Position 2

Position 1

If the actuator has missed the load, the
position complete output will not turn ON.