1.1.1 Explanation

of Signal Names

The following explains the signal names, and gives a function overview of each signal.
In the explanation of operation timings provided in a later section, each signal is referenced by its self-
explanatory name for clarity. If necessary, however, such as when marker tubes are inserted as a termination of
the flat cable, use the signal abbreviations.

 PIO pattern = 0 Positioning mode [Standard type]

Category Signal

name

Signal

abbreviation

Function overview

PC1
PC2
PC4
PC8
PC16

Command position
number

PC32

The target position number is input.
A command position number must be specified by 6 ms before the
start signal (CSTR) turns ON.

Brake release

BKRL

This signal is used on an actuator equipped with a brake to forcibly
release the brake.

Operating mode

RMDO

This signal switches the operating mode between AUTO and MANU.
(ON: MANU, OFF: AUTO)

Home return

HOME

Home return operation is started at a rise edge of this signal.

Pause

*STP

ON: Actuator can be moved, OFF: Actuator decelerates to a stop

Start

CSTR

The actuator will start moving at a rise edge of this signal.

Alarm reset

RES

An alarm is reset at a rise edge of this signal.

Input

Servo ON

SON

The servo remains ON while this signal is ON.
The servo remains OFF while this signal is OFF.

PM1
PM2
PM4
PM8
PM16

Completed position
number

PM32

The relevant position number is output when positioning has
completed.
The signal will turn OFF when the next start signal is received.
It is used by the PLC to check if the commanded position has
definitively been reached, and also to provide a position interlock, etc.

Moving MOVE

This signal will remain ON while the actuator is moving, and OFF
while the actuator is standing still.
Used to check the operation or determine if the load was missed in
push & hold operation.

Zone 1

ZONE1

This signal becomes effective after home return. It will turn ON when
the current actuator position enters the range set by the parameters
and remain ON until the actuator exits the range.

Position zone

PZONE

This signal becomes effective after a position movement command is
input. It will turn ON when the current actuator position enters the
range specified in the position table and remain ON until the actuator
exits the range.

Operating mode status

RMDS

A signal indicating the operating mode of AUTO or MANU is output.

Home return completion

HEND

This signal is OFF immediately after the power is input, and turns ON
when home return has completed.

Position complete

PEND

This signal turns ON when the actuator has moved to the target
position and entered the positioning band. It is used to determine if
the positioning has completed.

Servo-on status

SV

This signal is always output once the servo is turned ON and the
controller is ready to operate.

Emergency stop status

*EMGS

When this signal is OFF, it means that an emergency stop is being
actuated.

Alarm *ALM

This signal remains ON in normal conditions of use and turns OFF
when an alarm generates.

Output

Battery alarm

*BALM

This signal is ON when the absolute battery voltage is normal or an
incremental encoder is used.