IAI America SCON-C User Manual

Page 73

Advertising
background image




55


 PIO pattern = 1 Teaching mode [Teaching type]

Category Signal

name

Signal

abbreviation

Function overview

PC1
PC2
PC4
PC8
PC16

Command position
number

PC32

The target position number is input.
A command position number must be specified by 6 ms before the
start signal (CSTR) turns ON.

Operation mode

MODE

Mode selection (ON: Teaching mode, OFF: Normal mode)

Jog/inching switching

JISL

OFF: Jog, ON: Inching

+jog/inching movement

JOG+

The actuator will start jogging or inching in the positive direction at an
ON edge of this signal.

-jog/inching movement

JOG-

The actuator will start jogging or inching in the negative direction at an
ON edge of this signal.

Operating mode

RMOD

This signal switches the operating mode between AUTO and
MANU.

(ON: MANU, OFF: AUTO)

Home return

HOME

Home return operation is started at a rise edge of this signal.

Pause *STP

ON: Actuator can be moved, OFF: Actuator decelerates to a stop

Start CSTR

The actuator will start moving at a rise edge of this signal.

Current-position write

PWRT

When this signal has remained ON for 20 msec or longer, the current
position will be stored under the position number selected by PC1 to
PC32.

Alarm reset

RES

An alarm is reset at a rise edge of this signal.

Input

Servo ON

SON

The servo remains ON while this signal is ON.
The servo remains OFF while this signal is OFF.

PM1
PM2
PM4
PM8
PM16

Completed position
number

PM32

The relevant position number is output when positioning has
completed.
The signal will turn OFF when the next start signal is received.
It is used by the PLC to check if the commanded position has
definitively been reached, and also to provide a position interlock, etc.

Moving MOVE

This signal will remain ON while the actuator is moving, and OFF
while the actuator is standing still.
Used to check the operation or determine if the load was missed in
push & hold operation.

Mode status

MODES

This signal is ON when the controller is in the teaching mode, and
OFF when the controller is in the normal mode.

Position zone

PZONE

This signal becomes effective after a position movement command is
input. It will turn ON when the current actuator position enters the
range specified in the position table and remain ON until the actuator
exits the range.

Operating mode status

RMDS

A signal indicating the operating mode of AUTO or MANU is output.

Home return completion HEND

This signal is OFF immediately after the power is input, and turns ON
when home return has completed.

Position complete

PEND

This signal turns ON when the actuator has moved to the target
position and entered the positioning band. It is used to determine if
the positioning has completed.

Write completion

WEND

This signal is output upon completion of writing to the nonvolatile
memory in response to a current-position write command (PWRT).

Servo-on status

SV

This signal is always output once the servo is turned ON and the
controller is ready to operate.

Emergency stop status

*EMGS

OFF: Emergency stop has been actuated

Alarm *ALM

This signal remains ON in normal conditions of use and turns OFF
when an alarm generates.

Output

Battery alarm

*BALM

This signal is ON when the absolute battery voltage is normal or an
incremental encoder is used.