On installation of AK-04
[1] Use AK-04 in environment where surrounding air temperature is 0 to 40

C.

[2] The temperature of AK-04 increases by approximately 30

C during operation. Do not install multiple AK-04

converters closely or store them within ducts. Moreover, do not set them near other heating elements.

[3] When you use several AK-04 converters, lay them out separated for 10 mm or more.

A recommended installation example is shown below.
 Make the cable length between the host controller and pulse converter as short as possible.















 Keep pulse converters separated for 10 mm or more from each other.




















Host
controller

Wiring length: 50 mm or less is recommended.

10 mm or more

10 mm or more

If such layout cannot be
avoided, keep the wiring
length with the host
controller minimum.