IAI America SCON-C User Manual
Page 162
144
On installation of AK-04
[1] Use AK-04 in environment where surrounding air temperature is 0 to 40
C.
[2] The temperature of AK-04 increases by approximately 30
C during operation. Do not install multiple AK-04
converters closely or store them within ducts. Moreover, do not set them near other heating elements.
[3] When you use several AK-04 converters, lay them out separated for 10 mm or more.
A recommended installation example is shown below.
Make the cable length between the host controller and pulse converter as short as possible.
Keep pulse converters separated for 10 mm or more from each other.
Host
controller
Wiring length: 50 mm or less is recommended.
10 mm or more
10 mm or more
If such layout cannot be
avoided, keep the wiring
length with the host
controller minimum.