Zone signal output, 8 zone signal output – IAI America SCON-C User Manual

Page 138

Advertising
background image




120

3.8 Zone Signal Output


Two types of zone output signals are available: zone output (ZONE1) and position zone output (PZONE). The
boundaries defining the signal ON range are set differently for each zone output.
[1] Zone output (ZONE1) --- Set by parameter No. 1/No. 2.
[2] Position zone output (PZONE) --- Set in the “Zone boundary-“ and “Zone boundary+” fields of the position

table.

Whether these signals are available or not varies depending on the PIO pattern, as shown below.

: Available / x: Not available

PIO pattern

Signal classification

0 1 2 3 4 5

Zone output (ZONE1)

x x x 

Position zone output (PZONE)

x


Example of use in operation) Move the actuator from the home to the 150-mm position (position 1) and output a

zone signal once the actuator enters the range between 40 mm and 120 mm.

Method)

 Zone output (ZONE1)

The zone within which this signal turns ON is set by the Zone 1+ and Zone 1-
parameters.

Parameter No. 1

Zone 1+

120 (mm)

Parameter No. 2

Zone 1-

40 (mm)

 Position zone output (PZONE)

The signal ON range is set in the “Zone+” and “Zone-” fields of the position
table.

No.

Position

[mm]

Zone+

[mm]

Zone-

[mm]

0

* * *

1 150.00

120.00

40.00


* The zone functions have been changed due to version upgrade. Refer to the precautions at the outset.