IAI America SCON-C User Manual

Page 97

Advertising
background image




79


(5) Push

 Select either the positioning mode or push & hold mode.

The default setting is “0.”
0:

Positioning mode (= normal operation)

Other than 0: Push & hold mode [%]

 If the push & hold mode is selected, enter the current-limiting value to be

applied to limit the AC servo motor current during push & hold operation.

Caution: Take note that if the push force is too small, a false detection may occur during push & hold operation

due to sliding resistance, etc.



(6) Threshold

 This field is not used for this controller.

The factory setting is “0.”

(7) Positioning

band

 The meaning of this field varies

between “positioning operation” and
“push & hold operation.”
“Positioning operation”:
This field defines how much before
the target position the completion
signal will turn ON.
Increasing the positioning band
allows the next operation in the
sequence to be started early, and
consequently the tact time can be
reduced. Set an optimal value by
checking the overall balance of the
system.


“Push & hold operation”
This field defines the maximum push distance after reaching the target position
in push & hold operation.
Consider possible mechanical variation of the load and set an appropriate
positioning band that will prevent the positioning from completing before the
load is contacted.











The position complete signal turns ON here, as completion of
push action is recognized after the load has been contacted.

Load

Target position

Positioning band (maximum push distance)

The position
complete signal
turns ON here.

Positioning band

Target
position