IAI America SCON-C User Manual

Page 54

Advertising
background image




36


[2] Wiring and setting of safety circuit

[1] Power

supply

If a safety circuit is configured using safety relays and contactors of 24 V specifications, it is recommended to
use a separate power supply from the power supply for controllers of 24 V specifications (ACON, PCON etc.).
It can be configured using the common power supply between the two, but breakage may occur when falsely
wired.

[2] System I/O connector specification

 Connector used: MCDN1.5/6-G1-3.5P26THR (PHOENIX CONTACT)

 Cable side connector (accessory: initial wiring already conducted *):

FMC1.5/6-ST-3.5 (PHOENIX CONTACT)
Supported wire thickness: AWG24-16, recommended stripped wire length: 7 mm

Pin No.

Signal name

Explanation

1 EMG1-

2 EMG1+

Emergency stop contact 1
(30 VDC or less, 100 mA or less)

3 EMG2-

4 EMG2+

Emergency stop contact 2
(30 VDC or less, 100 mA or less)

5

EMGIN

Emergency stop detection input

Upper side

(EMG side)

6

EMGOUT

24 V power supply output for emergency stop detection input

7 ENB1-

8 ENB1+

Enable contact 1
(30 VDC or less, 100 mA or less)

9 ENB2-

10 ENB2+

Enable contact 2
(30 VDC or less, 100 mA or less)

11

ENBIN

Enable detection input

Lower side
(ENB side)

12

ENBOUT

24 V power supply output for enable detection input


* Connectors on the cable side are attached under conditions where initial wiring has been conducted.

In order to support each category, remove the initial wiring and wire your safety circuit.
 Upper side (EMG) connector

 Lower side (ENB) connector















Wiring Color

Signal

Yellow

Yellow

Yellow

Yellow

Wiring

Color

Signal

Yellow

Yellow

Yellow

Yellow