(8) Zone

+/-

 This field defines the zone in which PZONE (zone output signal) will turn ON

during operations in PIO pattern 0, 1, 2, 4 or 5.
To add flexibility, a different zone can now be set for each target position.

[Setting example]

No.

Position

[mm]

Zone+

[mm]

Zone-

[mm]

0 5.00 100.00

0.00

1

380.00 400.00 300.00

2

200.00 250.00 150.00


























* The zone functions have been changed due to version upgrade.

Refer to the precautions at the outset.


(9) Acceleration/deceleration

mode

 This field defines the acceleration/deceleration pattern.

The factory setting is “0.”

0: Trapezoid pattern
1: S-motion
2: Primary delay filter









* Set desired acceleration and deceleration in the “Acceleration” and

“Deceleration” fields of the position table.

Movement command to position No. 0

Movement command to position No. 1

Movement command to position No. 2

Trapezoid pattern

Speed

Acceleration

Deceleration

Time