<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-1

IM 01E30D01-01EN

9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)

This Chapter describes the device (AXR) operation

procedures using a HART configuration Tool (such

as FieldMate).

NOTE

For more details regarding the operations for

the HART configuration tool, refer to the HART

configuration tool operations manual.

Note: HART is a registered trademark of the HART

Communication Foundation.

9.1 HART Protocol Revision

For the models with the output signal code “-J”,

HART protocol revision 5 or 7 is selectable. The

protocol revision is set as specified in the order.

How to confirm protocol revision is shown below.

There are two ways to confirm the protocol revision

set to the transmitter.

(1) Confirmation by the name plate

The HART protocol revision at the time of

shipment is shown by the last number at the

serial number column of the name plate.

42

F0901.ai

XXX…XX 

5: HART 5

7: HART 7

(2) Confirmation by using HART configuration tool

Follow the procedure below.

1) Connect the configuration tool to the device.

2) Call up “Review4” display.

[Root Menu] → Review → Review4

3) HART protocol revision is displayed on the

“Universal rev” column.

IMPORTANT

Protocol revision supported by HART

configuration tool must be the same or higher

than that of the device.

Protcol revision

supported by HART

configuration tool

5

7

Protocol revision of

the device

5

7

×

: Communication OK

× : Communication NG

NOTE

• In this User’s Manual, HART protocol

revision 5 and 7 are described as HART 5

and HART 7 respectively.

• HART 7 communication is supported by

FieldMate R2.04 or later.

NOTE

When the output signal code of the device is “-J”,

HART protocol revision can be changed. Refer

to subsection 9.8.5 about the procedure of the

revision change of HART 5 and HART 7.

9.2 Device Description (DD) on

a HART Configuration Tool

and AXR Device Revision

9.2.1 DD Revision and Device Revision

Before using the HART Configuration Tool (such

as FieldMate), confirm that the DD (Device

Description) of the AXR is installed in the

Configuration Tool before using.

• AXR: HART 7

• Device type: 0x3757

• Device Revision: 10

• DD Revision: 1

The DD revisions for AXR and Configuration Tool’s

can confirm in accordance with the following steps.

If the correct DD is not installed in the HART