<6. PARAMETER DESCRIPTION>

6-17

IM 01E30D01-01EN

NOTE

If the flow rate units, time units, and flow

rate span are specified upon ordering, these

parameters will be setup before shipment;

however, if this is not the case, it will be

necessary for the appropriate values to be set up

by the user.

NOTE

Flow rate span is the value for instantaneous

flow rate that corresponds to a current output of

20 mA. The following factors should be taken

into consideration when deciding on the flow rate

span.

• In the case of applications with large

variations in flow rate, the maximum flow rate

should be set. If a flow rate in excess of the

flow rate span was to occur, output would be

possible up to an upper limit of 103.13%, and

beyond this, error would occur. Note that the

same applies to pulse output and totalization.

• In the case of applications that have a

relatively stable flow rate, a flow rate span of

1.5 to 2.0 times larger than the normal flow

rate may be considered suitable.

• The flow rate to be adopted should - upon

conversion to flow velocity - correspond to

a value within the range of 0.3 to 10 m/s.

The flow velocity can be confirmed using

sizing data or with parameter

C44: Velocity

Check, and in the latter case, the value

obtained when span is converted to flow

velocity will be displayed.

• Regardless of the position of the decimal

point, the largest value that can be set on the

display unit is 32,000. Furthermore, it is not

possible to set a number of 4 or greater for

the highest-order digit. Similarly, if 3 is set for

this highest-order digit, it will not be possible

to set a number of 2 or greater for the next

digit to the right, regardless of the position of

the decimal point.

Example: A value of 333.33 is represented

by the character string 33333, and

since this exceeds 32000, it cannot

be set. In such a case, the value

333.3 should be set instead.

[B24: Flow Decimal Pnt] Setting of the decimal

point position for the instantaneous flow rate

This setting is linked with that of parameter

C43.

This parameter sets the position of the decimal

point for instantaneous flow rate values in terms

of the number of digits. When set using “Auto”,

the decimal point position will be automatically

determined in accordance with the setting value for

B23/C42: Flow Span as shown below.

Flow Span ≤ 9

Decimal point position:

3 digits

9 < Flow Span ≤ 90

Decimal point position:

2 digits

90 < Flow Span ≤ 900 Decimal point position:

1 digit

900 < Flow Span

Decimal point position:

no digits (i.e., no decimal

point)

When an item other than “Auto” is set, the selected

number of digits for the decimal point position is

used.

With the decimal point removed, 6 digits are

available for the instantaneous flow rate value, and

display is possible up to 999,999. If an overflow

occurs as a result of the setting adopted for decimal

point position, the warning

84: Disp Over Wng will

be displayed to provide notification of this condition.

Example: When 1000 m

3

/h is set for B23/

C42: Flow Span

Item

Display content for instantaneous flow rate value

Auto

1000 m

3

/h

0

1000 m

3

/h

1

1000.0 m

3

/h

2

1000.00 m

3

/h

3

With the decimal point removed, 7 digits are not

available for the instantaneous flow rate value;

therefore, a warning is displayed.