5 wiring connections, Wiring connections -5, Important – Yokogawa ADMAG AXR User Manual

Page 29

Advertising
background image

<4. WIRING>

4-5

IM 01E30D01-01EN

F0410.ai

In case grounding rings

are used.

Hazardrous

area

Grounding ring

Non-hazardrous

area

Class A

grounding

In case grounding rings are

not used.

(Available only for metal piping)

[TIIS Explosion Proof Type]

• TIIS Explosion Proof Type: Grounding resistance of 10 Ω or less is

necessary for class A grounding

terminal.

Grounding resistance of 100 Ω or less

is necessary for Functional grounding

terminal.

When the optional code A is selected,

grounding resistance of 10 Ω or less

shall be required.

Figure 4.4.3 Grounding

IMPORTANT

Class A grounding should be installed in non-

hazardrous area.

4.5 Wiring Connections

(1) Removing Cover
The cover has the locking screws in front and

behind it as shown in Figure 4.5.1 in case of

explosion proof type. This is used for the cover-

lock system. Loosen cover locking screws

clockwise using a hexagonal wrench (nominal size

3) to unlock the cover. (Upon shipment from the

manufacturing plant, the cover is unlocked.)

Hold the flowmeter with your hand and remove the

cover by turning it in the direction of the arrow as

shown below (both explosion proof and general

purpose types).

F0411.ai

Cover locking

screws

Explosion proof type

Both Explosion proof and

General purpose types

Figure 4.5.1 Removing the Terminal Box Cover

(2) Terminal Configuration (General - purpose

Use/Explosion Proof Type except TIIS)

When the cover is removed, the connection

terminals will be visible.

F0412.ai

SUPPLY

DO

+

+



Figure 4.5.2 Terminal Configuration