<6. PARAMETER DESCRIPTION>

6-26

IM 01E30D01-01EN

NOTE

Multiple ranges setting
Parameters from

F20 to F31 are used with the

automatic multiple ranges. The followings will

describe the setting method for the range.

The multiple ranges use the following parameters:

[B23: Flow Span] Setting of the flow rate span

(Setting of the forward No.1 range)

[F20: Forward Span 2] Setting of the forward No.2

range

[F21: Reverse Span] Setting of the reverse range

[F30: Auto Range Hys] Setting of the automatic

multiple ranges hysteresis width.

[F31: Bi Direction Hys] Setting of the forward/

reverse flow measurement hysteresis width

Automatic multiple ranges switching

n

When the instantaneous flow rate exceeds

100% of the range, transition to the next range

(up to two ranges) is carried out automatically.

Furthermore, when the flow is in reverse, the

reverse range is automatically selected.

n

Range switching can be confirmed according to

the DO status output terminals. Refer to Table

6.4.1: Status Output for Automatic Multiple

Ranges Switching for details of status output

conditions for each range.

Status Output for Automatic Multiple Ranges

Switching

Operations are performed in accordance with the

following table when the active mode has been set

to “Closed (On) Act” using

F11: DO Active Mode.

Operating patterns are reversed when the active

mode has been set to “Open (Off) Act” using

F11:

DO Active Mode.

Table 6.4.1 Status Output for Automatic Multiple

Ranges Switching

[F10]

setting

Function

DO status

output

No

Function

Forward single

range

Fwd/Rev

Rngs

Auto forward/

reverse range

Forward

Reverse

Open

Closed

Auto 2

Rngs

Auto forward 2

ranges

Forward 1 range

Forward 2 range

Open

Closed

*: “No Function” is the default value. Only DO is used for single

or dual ranges.

Parameter setting sequence

(for automatic multiple ranges switching)

F0603.ai

F10: DO Function

Select a function.

Select a function (Note 1)

No Function: Output is stopped

Fwd/Rev Rngs: Forward/reverse flow rate

measurement

Auto 2 Rngs: Automatic 2-ranges switching

Refer to Table 6.4.1

and set

F10

B23: Flow

Span

Forward No.1 range

F20: Forward

Span 2

Forward No.2 range

F21:Reverse

Span

Reverse range

F11: DO Active Mode

Select whether DO output is to be “Closed (On) Act”

or “Open (Off) Act”.

If “instantaneous flow rate % (FR)” is selected for

Display Mode and

A10: FLOW RATE (%) is selected

for BRAIN communication, the instantaneous flow rate

% and following symbols will be displayed only for

multiple ranges and forward/reverse flow measurement.

Forward No.1 range: [F1]

Reverse : [R1]

Forward No.2 range: [F2]

Set the spans for the ranges to be used.

No.1 range ≤ No.2 range

Input

100%

No. 1 range

No. 2 range

Output

Reverse

Forward

Minimum span % within

forward/reverse (set using F31)

F0604.ai

10% of No. 1 range (set using F30)

Figure 6.4.1 Multiple Ranges and Hysteresis Widths