<6. PARAMETER DESCRIPTION>

6-7

IM 01E30D01-01EN

(5) Item E (Menu E): Pulse Setting items
Menu E contains items relevant to pulse output. This is used to set parameters such as the pulse scale and

width.

Item

Name

R/W

Data range

Units

Position

of decimal

point

Default value

(*): Indicated item

Description

Display unit

(BRAIN)

Display unit

/BRAIN

E00 Pulse Set

(PULSE SET)

E10 Pulse Unit

(PULSE UNIT)

W

n Unit/P

u Unit/P

m Unit/P

Unit/P

k Unit/P

M Unit/P

Pulse/s

Pulse/s (*)

Selects the flow rate unit per

one pulse as used for pulse

output. Linked with B32.

E11 Pulse Scale

(PULSE SCALE)

W

0 to 32000

E10

(B32)

0 to 4

0 (*)

Sets the flow rate per one

pulse as used for pulse output.

Linked with B33.

E12 Pulse Width

(PULSE WIDTH)

W

50% Duty

0.05 ms

0.1 ms

0.5 ms

1 ms

20 ms

33 ms

50 ms

100 ms

200 ms

330 ms

500 ms

1000 ms

2000 ms

50% Duty

Selects the pulse width for

pulse output.

E13 Pulse Low Cut

(PULSE LOWCUT)

W

0 to 100

%

0

3 %

Sets the range in vicinity of 0%

within which pulse output will

be halted.

E14 Pulse Rate Check

(PLS RATE CHK)

R

0 to 999999

Pulse/s

0 to 5

0.0

Displays the pulse output rate

in “Pulse/s”

E60 —

(SELF CHECK)

R

Good

Error

See “6.5 Alarm Function”.