<6. PARAMETER DESCRIPTION>

6-27

IM 01E30D01-01EN

NOTE

For more details regarding the setting of

hysteresis width, refer to the description of

setting parameter for

F30: Auto Range Hys and

F31: Bi Direction Hys.

[F30: Auto Range Hys] Setting of automatic range-

switching hysteresis width

Automatic switching takes place for multiple range

switching when 100% of the range is exceeded,

and this parameter allows a hysteresis width to be

set for this switching.

Refer to Figure 6.4.1: Multiple Ranges and

Hysteresis Widths.

[F31: Bi Direction Hys] Setting of forward/reverse

flow measurement hysteresis width

This parameter sets the hysteresis for forward/

reverse flow rate measurement as a % value of the

minimum flow span.

Refer to Figure 6.4.1: Multiple Ranges and

Hysteresis Widths.

(6) Menu G: Alarm Setting items

(Refer to Section 6.5: Alarm Functions for more

details.)

Menu G principally contains setting items relevant

to alarms.

[G10: Low Alarm] Low alarm setting

This parameter sets the low limit (L) alarm value,

and this is done using a % value of the maximum

span.

A

setting value of -105% indicates that the

alarm is disabled.

[G11: High Alarm] High alarm setting

This parameter sets the high limit (H) alarm value,

and this is done using a % value of the maximum

span.

A setting value of 105% indicates that the alarm

is disabled.

Output Example 1

The high alarm (H) is set to 80% or more; the low

alarm (L) is set to 30% or less; and the H/L alarm

hysteresis width is set to 0%.

Settings are:

G10: Low Alarm = 30%

G11: High Alarm = 80%

G12: H/L Alarm Hys = 0%

0

Time (t)

Select “H/L Alarm(O)” for

F10: DO Function

Select “Closed (On) Act” for

F11: DO Active Mode

Select “Yes” for

G28: Alm-H/L

DO

Open

Closed

Open

Open

Closed

High Alarm

Instantaneous flow rate

Low Alarm

30

50

80

100

[%]

F0605.ai