Page 97: Bt200 connection -3, 2 axr operation using a bt200, Warning, Important

Advertising
background image

<7. OPERATION VIA BRAIN TERMINAL (BT200)>

7-3

IM 01E30D01-01EN

7.2 AXR Operation Using a

BT200

This section describes procedures for setting

parameters using a BRAIN Terminal (BT200). For

more details regarding AXR functions, refer to

Chapter 6: Parameter Description; and for more

details regarding BT200 operation methods, refer to

the BT200 User’s Manual (IM 01C00A11-01E).

7.2.1 BT200 Connection

Connection to a 4 to 20 mA DC signal line

The communication signal is superimposed onto

the 4 to 20 mA DC analog signals to be transmitted.

AXR terminals

BT200

BT200

Relaying

terminals

4 to 20 mA

DC signal

transmission

line

Control room

Distributor

Receiving

instrument

Terminal

board

F0707.ai

BT200

SUPPLY

DO

Figure 7.2

Connecting the BT200

WARNING

Be sure to set parameters as “Protect” on the

write protect function after finish of parameter

setting work.

Refer to “Chapter 6 Menu P: Parameter

Protection items” and section “11.3.2” how to use

the write protect function in detail.

IMPORTANT

Restrictions exist with regard to the distance

over which communication is possible. When

simultaneous output of current and pulse output

or pulse output are used, no communication is

possible depending on the wiring. Refer to 4.6

Wiring Procedure and Chapter 12: Outline in

detail.

IMPORTANT

If the power of flowmeter is turned off within 30

seconds after parameters have been set, these

settings will be canceled. Accordingly, please

keep the power on for at least 30 seconds after

setting parameters.

IMPORTANT

After approximately 5 minutes of inactivity, the

Auto Power-Off function will operate to turn your

BT200 off.

NOTE

In case of BT200, the parameters are displayed

in English only.

Even if the language with the exception of

English is selected at

B10/H30: Language,

the parameters are displayed in English upon

BT200.