Yokogawa ADMAG AXR User Manual

Page 60

Advertising
background image

<6. PARAMETER DESCRIPTION>

6-12

IM 01E30D01-01EN

(9) Item J (Menu J): Auxiliary Function Setting items
Menu J contains setting items such as the flow direction, rate limits, and low cut.

Item

Name

R/W

Data range

Units

Position

of decimal

point

Default value

(*): Indicated item

Description

Display unit

(BRAIN)

Display unit

/BRAIN

J00 Aux

(AUX)

J10 4-20mA Low Cut

(4-20 LOW CUT)

W

0 to 20

%

0

3%

Sets the range in vicinity of 0%

within which the current output

will be 4 mA.

J11 4-20mA Low Lmt

(4-20 LOW LMT)

W

-1.25 to 100.00

%

2

-1.25%

Sets the low limit for current

output

J12 4-20mA High Lmt

(4-20 HI LMT)

W

0.0 to 103.13

%

2

103.13%

Sets the high limit for current

output

J15 Pls Special Mode

(PLS SPECIAL)

W

Normal

Pulse Only

Normal

Selects the pulse special mode

J20 Flow Direction

(FLOW DIRECT)

W

Forward

Reverse

Forward

Selects the flow direction.

J21 Rate Limit

(RATE LIMIT)

W

0 to10

%

0

5%

Sets the level to reduce output

fluctuation.

J22 Dead Time

(DEAD TIME)

W

0 to 15

s

0

0s

Sets the dead time to reduce

output fluctuation. When “0”

is set, rate limit function is not

available.

J23 Pulsing Flow

(PULSING FLOW)

W

No

Yes

No

Selects whether pulsing flow is

to be supported.

J25 T/P Damp Select

(T/P DAMP SEL)

W

Damping

No Damping

Damping

Selects whether the flow

rate value obtained through

damping calculation for total/

pulse or the instantaneous flow

rate value (no damping) for

total/pulse is to be used.

J30 Basic Frequency

(BASIC FREQ)

W

Freq(1)

Freq(2)

Freq(1)

Selects the basic frequency

J35 Memo 1

(MEMO 1)

W

ASCII 16 characters

Memo field

J36 Memo 2

(MEMO 2)

W

ASCII 16 characters

Memo field

J37 Memo 3

(MEMO 3)

W

ASCII 16 characters

Memo field

J40 MS Code 1

(MS CODE 1)

W

ASC II 16 characters

Sets MS code 1

J41 MS Code 2

(MS CODE 2)

W

ASCII 16 characters

Sets MS code 2

J42 MS Code 3

(MS CODE 3)

W

ASCII 16 characters

Sets MS code 3

J43 MS Code 4

(MS CODE 4)

W

ASCII 16 characters

Sets MS code 4

J44 MS Code 5

(MS CODE 5)

W

ASCII 16 characters

Sets MS code 5

J45 MS Code 6

(MS CODE 6)

W

ASCII 16 characters

Sets MS code 6

J50 Software Rev No

(SOFTWARE REV)

R

Software revision number

J60 —

(SELF CHECK)

R

Good

Error

See “6.5 Alarm Functions”.

Advertising