<6. PARAMETER DESCRIPTION>

6-29

IM 01E30D01-01EN

[G25: 4-20mA Process Alarm] Selection of the

current output during a process alarm occurrence

This parameter sets the current output during a

process alarm occurrence.

Setting

Function

21.6 mA or More Fixed at 21.6 mA or more

20.5 mA

Fixed at 20.5 mA

Hold

Fixed current value when an alarm

occurred.

4.0 mA

Fixed at 4.0 mA

3.8 mA

Fixed at 3.8 mA

3.2 mA or Less

Fixed at 3.2 mA or less

The default parameter is set to the following table at

the factory.

Standard

Optional code C1

21.6 mA or More

3.2 mA or Less

[G26: Alm-Sig Over] Alarm recognition of “Signal

Overflow Alarm”

This parameter specifies whether the signal

overflow in process alarms will be recognized as

an alarm. A signal overflow occurs when there is an

error in the input signal.

Setting

Function

No

Not recognized as an alarm

Yes

Recognized as an alarm

[G27: Alm-Emp Pipe] Alarm recognition of “Empty

Pipe Alarm”

This parameter specifies whether the empty pipe

(flowtube is not filled with fluid) in process alarms

will be recognized as an alarm.

Setting

Function

No

Not recognized as an alarm

Yes

Recognized as an alarm

[G28: Alm-H/L] Alarm recognition of “H/L Alarm”

This parameter specifies whether H/L alarm in

process alarms will be recognized as an alarm.

Setting

Function

No

Not recognized as an alarm

Yes

Recognized as an alarm

NOTE

To set “H/L Alarm” as an alarm, it is necessary to

set “H/L Alarm” according to

F10: DO Function,

and set

G10: Low Alarm or G11: High Alarm as

well.

[G29: Alm-Adhesion] Alarm recognition of

“Adhesion Alarm”

This parameter specifies whether the electrode

adhesion alarm in process alarms will be

recognized as an alarm.

Setting

Function

No

Not recognized as an alarm

Yes

Recognized as an alarm

[G30: 4-20mA Setting Alarm] Selection of the

current output during a setting alarm occurrence

This parameter sets the current output during a

setting alarm occurrence.

Setting

Function

21.6 mA or more Fixed at 21.6 mA or more

20.5 mA

Fixed at 20.5 mA

Hold

Fixed current value when an alarm

occurred.

4.0 mA

Fixed at 4.0 mA

3.8 mA

Fixed at 3.8 mA

3.2 mA or Less

Fixed at 3.2 mA or less

The default parameter is set to the following table at

the factory.

Standard

Optional code C1

21.6 mA or More

3.2 mA or Less