<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-10

IM 01E30D01-01EN

b) Acknowledge Event Notification
Execute

Acknowledge Event Notification

method.

1) Enter “the event number which is confirmed

in a) 5” into “Enter Event Number”.

2) OK.

3) Set “Select Transaction” to “Trans 1 : Send

Acknowledge”.

4) OK.

5) Confirm “Even Status” is 0x00.

(3) Event Notification Record (DTM only)

• Procedure to call up the display

DTM

[Root Menu] → Detailed setup →

Output condition →HART output

→ Burst condition → Event

Notification → Event knowledge

→ Acknowledge

Event Notification

Acquisition of the event number

and approval.

a) Get Event Number
Confirm the latest event number.

Execute

Acknowledge Event Notification

method.

1) Set “Enter Event Number” to “0”.

2) OK.

3) Set “Select Transaction” to “Trans 0: Read

Event Notification”.

4) OK.

5) Confirm “Event Number”.

b) Confirmation record of Event Notification
Confirm four events checked in a).

Execute

Acknowledge Event Notification

method.

1) Enter “the event number which is confirmed

in a) 5” into “Enter Event Number”.

2) OK.

3) Set “Select Transaction” to “Trans 0:Read

Event Notification”.

4) OK.

5) Knowledge menu displays events record.

Ex.) When the confirmed event number is 123.

Event Number

Explanation

123

The latest event

122

An event before the once.

121

An event before the twice.

120

An event before three times.

9.8.4 Multidrop Mode

“Multidropping” transmitters refer to the connection

of several transmitters to a single communication

transmission line. Up to 63 transmitters can be

connected when set in the multidrop mode. To

activate multidrop communication, the transmitter

address must be changed to a number from 1 to

63. This change deactivates the 4 to 20 mA analog

output, sending it to 4 mA. The alarm current is also

disabled.

Setting of Multidrop Mode

(1) Polling address

• Procedure to call up the display

DD

DTM

[Root Menu] → Detailed setup

→Output condition →HART

output →

→ Poll addr

Enter the number from 1 to 63

(2) Enabling the Multidrop Mode
About the procedure to call up the

Polling

display, please refer to the User’s Manual of each

configuration tool.
When

Loop current mode is set to “Enabled”, an

analog signal output is available for one device in a

loop.

• Procedure to call up the display

DD

DTM

[Root Menu] → Detailed setup →

Output condition →Analog output →

Loop current mode →

Enabled

Loop current mode is enabled.

Disabled

Loop current mode is disabled.

NOTE

When the same polling address is set for

two or more transmitters in multidrop mode,

communication with these devices is disabled.

(3) Communication when set in multidrop

mode.

• The HART configuration tool searches for a

device that is set in multidrop mode when it is

turned on. When the HART configuration tool

is connected to the device, the polling address

and the tag will be displayed.

• Select the desired device. After that, normal

communication to the selected device is

possible. However, the communication speed

will be slow.