<6. PARAMETER DESCRIPTION>

6-24

IM 01E30D01-01EN

Data Range

Setting

Pulse Rate (pps)

Maximum Value

Minimum Value

(0) 50% Duty 11000

0.0001

(pps: pulses per

second)

(1) 0.05ms

10000

(2) 0.1ms

5000

(3) 0.5ms

1000

(4) 1ms

500

(5) 20ms

25

(6) 33ms

15

(7) 50ms

10

(8) 100ms

5

(9) 200ms

2.5

(10) 330ms

1.5

(11) 500ms

1.0

(12) 1000ms

0.5

(13) 2000ms

0.25

NOTE

*: The pulse width with the exception of “50%

Duty” is the “Closed (On)” time for each pulse

in case that “Closed (On) Act”. Refer to the

example 1 of

F11: DO Active Mode.

A limit applies to the maximum pulse scale

that can be set with respect to the pulse width.

If a value in excess of this limit is set, a setting

alarm will be displayed.

[E13: Pulse Low Cut] Setting of the pulse output

stop range

This parameter allows the setting to be made which

prevent pulse output when the flow rate is at or

below the low-cut setting value.

The low cut setting value depends on flow rate

span.

● Flow rate span < 1 m/s:

Input value or 3 cm/s, whichever is bigger

● Flow rate span ≥ 1 m/s:

Input value

To confirm the flow rate span velocity in ”m/s” unit,

see

[C44: Velocity Check].

If the multiple ranges or forward/reverse ranges is

used, low cut is carried out at the setting value for

the smallest span.

However, the low cut function will be terminated if

this parameter is set to “0 %”.

NOTE

When the low cut is small, an incorrect output

may occur at the flow rate of zero and a

pulse may be output. Use the instrument with

the default setting 3%. If the span is small,

the damping time is short, or the fluid is low

conductivity, a pulse may be output easily at the

flow rate of zero. In this case, set the span to be

large, set the damping time to be long, or set the

low cut to be large.

[E14: Pulse Rate Check] Display of the pulse

output rate in “Pulse/s”

This parameter displays the pulse output rate,

which is converted to “Pulse/s” while 100% of the

range flows.

When the multiple ranges or forward/reverse

ranges are used, the AXR displays the pulse output

rate which 100% of their maximum range flows.