<6. PARAMETER DESCRIPTION>

6-9

IM 01E30D01-01EN

(7) Item G (Menu G): Alarm Setting items
Menu G contains setting items relevant to alarm output, burnout, alarm record, etc.

Item

Name

R/W

Data range

Units

Position

of decimal

point

Default value

(*): Indicated item

Description

Display unit

(BRAIN)

Display unit

/BRAIN

G00 Alarm

(ALARM)

G10 Low Alarm

(LOW ALARM)

W

-105 to 105

%

0

-105%

Sets level setting value for low

flow rate limit (L)

G11 High Alarm

(HIGH ALARM)

W

-105 to 105

%

0

105%

Sets level setting value for high

flow rate limit (H)

G12 H/L Alarm Hys

(H/L ALM HYS)

W

0 to 10

%

0

5 %

Sets hysteresis width for high-

low flow rate limit alarm

G20 4-20 System Alm

(4-20 SYS ALM)

R

21.6mA (see IM)

3.2mA (see IM)

21.6mA (see IM)

(*)

Displays the current output

during a system alarm

occurrence

G25 4-20 Process Alm

(4-20 PRO ALM)

W

21.6mA or More

20.5mA

Hold

4.0mA

3.8mA

3.2mA or Less

21.6mA or More (*) Selects the current output

during a process alarm

occurrence

G26 Alm-Sig Over

(ALM-SIG OVER)

W

No

Yes

Yes

Selects whether a signal

overflow alarm is to be

specified as an alarm.

G27 Alm-Emp Pipe

(ALM-EMP PIPE)

W

No

Yes

No

Selects whether an empty pipe

alarm is to be specified as an

alarm.

G28 Alm-H/L

(ALM-H/L)

W

No

Yes

No

Selects whether a flow rate

high or low alarm is to be

specified as an alarm.

G29 Alm-Adhesion

(ALM-ADHESION)

W

No

Yes

No

Selects whether an electrode

adhesion alarm is to be

specified as an alarm.

G30 4-20 Setting Alm

(4-20 SET ALM)

W

21.6mA or More

20.5mA

Hold

4.0mA

3.8mA

3.2mA or Less

21.6mA or More (*) Selects the current output

during a setting alarm

occurrence

G31 Alm-Setting

(ALM-SETTING)

W

No

Yes

Yes

Selects whether a setting alarm

is to be specified as an alarm.

G35 Alarm Display

(ALM DISPLAY)

W

Normal

NE107

Normal

Selects alarm display form

on the display unit and

configuration tools.

G40 Operation Time

(OPERATE TIME)

R

0D 00:00 to

9999D 23:59

Operation time

G41 Alm Record1

(ALM RECORD1)

R

10:uP Fault

11:EEPROM Fault

12:Sub uP Fault

13:EX Pwr Fault

14:A/D(S) Fault

15:A/D(I) Fault

16:Analog Fault

17:Coil Open

18:Coil Short

19:Excite Error

20:Pulse Error

21:EEPROM Dflt

22:Power Off

23:Inst Pwr Fail

28:WDT

30:Sig Overflow

31:Empty Pipe

33:Adhesion Alm

91:Disp Cur Wng

Displays the content of the

most recent alarm.