4.4 Grounding Connection

IMPORTANT

Grounding resistance of 100 Ω or less is

necessary. When the optional code A is selected,

grounding resistance of 10 Ω or less shall be

required.

In case of TIIS explosion proof type, grounding

resistance of 10 Ω or less is necessary for class

A grounding terminal.

Grounding resistance of 100 Ω or less is

necessary for Functional grounding terminal.

For explosion proof type except TIIS, follow the

domestic electrical requirements as regulated in

each country.

Grounding terminals

F0407.ai

Figure 4.4.1 Functional Grounding Terminal

Location (General - purpose Use/

Explosion Proof Type except TIIS)

Class A grounding

Grounding

terminal

F0408.ai

Figure 4.4.2 Functional Grounding Terminal

Location (TIIS Explosion Proof Type)

IMPORTANT

Improper grounding can have an adverse effect

on the flow measurement. Ensure that the

instrument is properly grounded.

The electromotive force of the magnetic flowmeter

is minute and it is easily affected by noise, and

the reference electric potential is the same as that

of the measuring fluid. Therefore, the reference

electric potential (terminal potential) of the flowtube

and converter also need to be the same as that of

the measuring fluid. Moreover, the potential must be

the same as the ground. The magnetic flowmeter

is equipped with a grounding ring that makes a

connection with the charge of the measured fluid

for grounding and protects the lining. The flowmeter

should be grounded by certain specifications

(grounding resistance of 100 Ω or less, or 10 Ω or

less) according to Figure 4.4.2.

Grounding is mandatory especially for insulated

piping such as PVC-sheathed pipes. If not, the

magnetic flowmeter measures the flow incorrectly

because the reference electrical potential is floating.

Moreover, grounding is also mandatory in the

simultaneous outputs of current and pulse. If not,

the flowmeter causes a large measurement error

because the outputs interfere with each other.

F0409.ai

600 V vinyl-insulated cable

(2 mm

2

or larger)

[General - purpose Use/Explosion Proof Type

except TIIS]

• Class D requirements (ground resistance,

100 Ω or less).

Optional code A (lighting protector): Class C

requirements (ground resistance, 10 Ω or less).

• Explosion proof type except TIIS: Domestic

electrical requirements as regulated in each

country.