<6. PARAMETER DESCRIPTION>

6-32

IM 01E30D01-01EN

(8) Menu J: Auxiliary Function Setting items
Menu J contains setting items such as the flow

direction, rate limits, and current output limits.

[J10: 4-20mA Low Cut] Setting of the low-cut

range for current output

This parameter is used to force current output to

0 % (i.e., 4 mA) in the vicinity of 0% output, and

setting for the current (4 to 20 mA) output low cut is

made using a percentage of the smallest flow rate

span.

The low cut setting value depends on flow rate

span.

● Flow rate span < 1 m/s:

Input value or 3 cm/s, whichever is bigger

● Flow rate span ≥ 1 m/s:

Input value

To confirm the flow rate span velocity in “m/s” unit,

see

[C44: Velocity Check].

Example 1: Situation where the flow rate span is set

to 2 m/s:

When “10 %” is input in this parameter, low cut

setting value is to be “10 %”.

F0608.ai

Setting range: 0 to 20%

4mA

Output

Input

0.5% 0.5%

10%

10%

Setting value

Hysteresis
fixed at 1%

5.6mA(10%)

Example 2: Situation where the flow rate span is set

to 0.8 m/s:

When “3 %” is input in this parameter, low cut

setting value is to be “3 cm/s”.

F0608-2.ai

Setting range: 0~20%

4mA

Output

Input

0.5% 0.5%

3%

3cm/s

3cm/s

Input value:3%(=2.4cm/s)

Setting value

Hysteresis
fixed at 1%

4.6mA(3.75%)

If the multiple ranges or forward/reverse ranges is

used, low cut is carried out at the setting value for

the smallest span.

However, the low cut function will be terminated if

this parameter is set to 0 %.

The indications of the instantaneous flow rate (%,

Actual instantaneous flow rate, mA, Bar graph) on

the display unit are the same action.

NOTE

The default setting is 3%.

When the low cut is small, an incorrect output

may occur at the flow rate of zero. Use the

instrument with the default setting 3%. If the span

is small, the damping time is short or the fluid is

low conductivity, an incorrect output may occur

easily at the flow rate of zero.

[J11: 4-20mA Low Lmt] Setting of the low limit for

current output

This parameter is used to restrict low current

portions of current (4 to 20mA) output, and it is

initially set to -1.25%. Setting should be performed

when a higher value is required for the lower limit.

The indications of the instantaneous flow rates (%,

Actual instantaneous flow rate, mA, Bar graph) on

the display unit are the same action.
Example: Situation where low limit is set to 10%

F0609.ai

4mA

Output

Input

5.6mA(10%)

NOTE

When the low limit works, the display indicates

83:Fix Cur Wng as the warning.

NOTE

The set current output at each alarm function

becomes higher priority than set value at

J11

when the alarm occurs.

The priority of this output is described below.

The process alarms and setting alarms are

available when “Yes” were selected at

G26, G27,

G28, G29 and/or G31.

System alarm (

G20) >

Process alarm (

G25) >

Setting alarm (

G31) >

Low limit (

J11)

Example: “3.8mA” is set for

G25

The current output is 3.8mA in spite of

setting any value at

J11.