5 switching hart protocol revision, 6 other operations for the hartconfiguration tool, Switching hart protocol revision -11 – Yokogawa ADMAG AXR User Manual

Page 130: Important

Advertising
background image

<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-11

IM 01E30D01-01EN

To release multidrop mode, call up the

Poll addr

display and set the address to “0” and set the Loop

current mode to “Enabled”.

9.8.5 Switching HART Protocol Revision

When the output signal code is “-J”, HART protocol

revision of the device can be selectable from 5 or 7.

The HART protocol revision is set and shipped as

specified in the order.

To change the HART protocol revision after

shipment, follow the procedure shown below.

IMPORTANT

When changing the protocol revision, confirm the

items below.

• Protocol revision supported by HART

configuration tool must be the same or

higher than new protocol revision of the

device.

• Confirm that the DD or DTM which is suitable

to new protocol revision of the device is

installed in the configuration tool. (Refer to

Section 9.2)

1) Call up the parameter for protocol revision

change

• Procedure to call up the

Chg universal rev

display.

DD

DTM

[Root Menu] → Detailed setup →

Device information → Field device

information → Revision #’s → Chg

universal rev

2) Activate the “Chg universal rev” method

IMPORTANT

The message is displayed to separate the device

from the automatic control loop.

Confirm that the device is separated.

3) Input the new revision number

An input column for new protocol revision number is

displayed.

Input the new HART protocol revision number of “5”

for HART 5 or “7” for HART 7.

4) Applying the new protocol revision

a. Close the configuration tool

After completion of Chg universal rev

method, close the HART configuration tool.

NOTE

When using a FieldMate, close the main display

of FieldMate.

b. Restart the device

Turn off the power to the device, and turn it

on.

IMPORTANT

New protocol revision is applied only after having

performed restart of the transmitter.

5) Confirming the new protocol revision

a. Restart the HART configuration tool

NOTE

When execute the other parameter confirmation

or setting change, execute after restart the

configuration tool.

b. Confirm the new HART protocol revision

number

Call up the

Universal rev parameter, and confirm

that the new HART revision number is displayed.

• Procedure to call up the

Universal rev.

parameter.

DD

DTM

[Root Menu] → Detailed setup

→ Device information → Field

device information → Revision #’s

→ Universal rev →

5

HART protocol revision: 5

7

HART protocol revision: 7

HART protocol revision can also be confirmed on

the second line and third line of the device display.

• Procedure to call up the

Display Select

DD

DTM

[Root Menu] → Detailed Setup →

Function Set → Display Set →

→ Display

Select2 or

Display Select3

Select “Communication”

Protocol Revision

Displayed on AXR screen

HART Protocol Revision 5

HART5

HART Protocol Revision 7

HART7

9.8.6 Other operations for the HART

configuration tool

Regarding other operations for the HART

configuration tool, refer to the HART configuration

tool operations manual.

Advertising