<11. MAINTENANCE>

11-7

IM 01E30D01-01EN

11.4.1 Adhesion Diagnostic Using Display Unit Switches

This section describes the procedure for Adhesion Diagnostic using the display unit switches. (For more details

regarding setting methods using these switches, refer to Chapter 5: Basic Operating Procedures.)

The parameters that are relevant to the adhesion diagnostic function are as follows.

[K10:Adhesion Check] Execution of adhesion diagnostic function

[K11:Adhesion Status] Display of the adhesion diagnosis level

[K12:Adh Measure Value] Displays the resistance value for adhesion diagnose

[K13:Adhesion Level1] Setting the resistance value for adhesion diagnostic level1

[K14:Adhesion Level2] Setting the resistance value for adhesion diagnostic level2

[K15:Adhesion Level3] Setting the resistance value for adhesion diagnostic level3

[K16:Adhesion Level4] Setting the resistance value for adhesion diagnostic level4

[K17:Adhesion Check Cycle] Setting of execution time for adhesion diagnosis

For more details regarding these parameters, refer to Chapter 6: Parameter Description.

The parameter for executing the adhesion diagnostic function is

K10:Adhesion Check.

The parameter

K10:Adhesion Check will be used in the following description.

Setting Mode

Major item

parameter

Setting mode

J:Aux

K:Diagnosis

M:Adjustment

K10:Adhesion Check

No Execution

No Execution

Execution

K10:Adhesion Check

No Execution

Execution

No Execution

Major item

Sub-item

selection (D)

K10:Adhesion Check

Execution

Sub-item

Parameter

Search Mode

Parameter

Replacement

(execute) Mode

Start:

Major Item

Parameter

Search Mode

K:Diagnosis

23:Empty Level

10:Adhesion Check

11:Adh Status

F1109.EPS

SET

SET

INC

SET

SET

Once in Setting Mode, use the

INC

switch to

move the cursor to

K: Diagnosis.

Touch the

SET

switch to access Sub-item

Parameter Search Mode.

Upon selection of

K: Diagnosis, the cursor will be

positioned at

K10: Adhesion Check. (Sub-item

selection (D)).

Touch the

SET

switch to access Parameter

Replacement Mode.

Touch the

INC

switch to move the cursor to

“Execution”.

Touch the

SET

switch to select the “Execution”.

In order to request confirmation, the entire display

flashes on and off. Touch the

SET

switch once

again at this time to fix selection of the Adhesion

Diagnosis function.

NOTE

When no operations are carried out for 20

seconds in the flashing state, the system will

automatically return to the Sub-item Parameter

Search Mode.

When the operations except

SET

are carried

out, the parameter cannot be set.