Error

number

Error code

Cause

Remedy

64

CE3

CAN-IN3 channel is not receiving any
data or is receiving erroneous data

Check CAN bus cable (connector X4)
Check CAN terminating resistor (on the first and last
CAN station)
Check configuration of the CAN node sending on CAN-
IN3
Check power supply to the CAN node sending on CAN-
IN3
Check monitoring time in code C0357/003 and increase
if necessary

65

CE4

Controller has received too many
erroneous messages over the CAN bus
and has disconnected itself from the bus

Check baud rate of all nodes
Check wiring:
-

Check bus terminating resistors

-

Check shield connection on the cables

- Check

PE

connection

-

Check bus load (e.g. using software tool
PCANView)

-

Reduce baud rate (CAUTION: pay attention to
CAN bus cable lengths)

66

CE5

CAN time-out (gateway function C0370)

Check settings in C0370.

70

U15

Undervoltage internal 15 V supply
voltage

Check servo axis voltage supply.

Processor is overloaded or program
execution problem

Reduce processor load: remove unnecessary function
blocks from the processing table (C0465/0xx)

Heavy interference on the control cables Lay control cables screened

71

CCr

Earth loop in the wiring

Wire as per EMC requirements (see System Manuals
"9300", p. 4-34)

72


Pr1


Error on transferring the parameter set
CAUTION: default setting is loaded
automatically!

Set the required parameters and save safe against
mains failure in the EPROM using code C0003/000

74

PEr

Error in the internal program execution

Read parameter set and send together with the source
project to Lenze for further analysis, consultation with
Lenze necessary (service hotline: (+49) 5154 82-1111)

75

Pr0

Invalid data in the EEPROM on loading
the parameters from the EEPROM to the
RAM
CAUTION: default setting is loaded
automatically!

Set the required parameters and save safe against
mains failure in the EPROM using code C0003/000, then
switch mains/shutdown the control voltage once

Error on transferring the parameters from
the EEPROM to the RAM

Read parameter set and send together with the source
project to Lenze for further analysis, consultation with
Lenze necessary (service hotline: (+49) 5154 82-1111)

79

PI

Use of a parameter set in the GDC
software that does not match the device
(9300EI/ET).

Use parameter set that matches the controller in the
GDC software, transfer this again to the controller and
save safe against mains failure in the controller using
C0003/000, then switch mains/shutdown the control
voltage once

Resolver cable partially or entirely open
circuit/disconnected

Check resolver cable for wire breakage
Check resolver

82

Sd2

Resolver not fitted/not connected

Disable monitoring via the code C0586/000 = 3, if a
resolver is not used

Encoder cable open circuit

Disconnect cable from X9 and check for wire breakage

83

Sd3

Pin 8 on input X9 open circuit

Apply +5V DC to pin 8 on input X9
OR:
Disable monitoring using code C0587/000 = 3

85

Sd5

Current master value on X6 (terminals 1
and 2) less than 2mA

Check cable for wire breakage
Check master current value encoder
Check setpoint configuration using C0034/000
OR:
Disable monitoring using code C0598/000 = 3

86

Sd6

Motor temperature sensor on X8 is
providing undefined values

Check cable on X8 for correct seating and wire breakage
Disconnect thermocouple (PTC/KTY) and measure
resistance (must not be

∞)

OR:
Disable monitoring using code C0594/000 = 3

87

Sd7

Absolute value encoder with RS485
interface is not sending any data

Check cable on X8 for correct seating and wire breakage
Check absolute value encoder for correct function
Set supply voltage to 8.0V using C0421/000
Encoder with HIPERFACE interface not connected

CAUTION: after rectifying the cause of the error, fully
isolate the servo controller