4-11 Assembly and Installation

Publication 825-UM001B-EN-P January 2001

Figure 4.14 Cat. No. 825-MMV Option Card

Method of Installation

Short links (up to 10 m) laid separate from power cables need no screening.

Longer leads must be screened/shielded

Separately screened: connect screens to individual T2 (e.g., 1T2, 2T2…)

Common screening: connect screen to T2, and all T2 together (e.g., 1T2, 2T2…)

ATTENTION

!

Either the 825-MLV or 825-MMV option cards may be inserted in
this position.

1T1

1T3

1T2

PT100 #1

PT100 #2

PT100 #3

PT100 #4

PT100 #5

PT100 #6

PT100 #7

2T1

2T3

2T2

3T1

3T3

3T2

4T1

4T3

4T2

5T1

5T3

5T2

6T1

6T3

6T2

7T1

7T3

7T2

PT100 inputs #1…#6 (RTD) for
monitoring the temperature of the stator
winding and motor bearings.

PT100, #7 for indication and inclusion of
the coolant/ambient temperature (cooling
air) in the thermal image. If PT100 #7 is
not connected, then a resistance of
120

should be connected between T1

and T3.

Tamb IN TH IMAGE
OFF