Main circuit, Figure 9.10 – Rockwell Automation 825 Smart Motor Manager User Manual User Manual

Page 150

Advertising
background image

9-9 Applications/Wiring

Publication 825-UM001B-EN-P January 2001

Basic Unit and Converter Module with Primary Current
Transformer and Core Balance Current Transformer

Main Circuit

Figure 9.10 Typical Application Utilizing Primary Current Transformers and Core
Balance Current Transformer

k

M

3~

T2

T1

1

3

5

2

4

6

825-MCM

825-M

Σ

L1

L2

L3

l

Converter module
Cat. No. 825-MCM2
Cat. No. 825-MCM20

T1 Primary Current Transformer
…A/5 A or …A/1 A (Selection refer to

Chapter 2

,

Specifications — Basic Unit and Converter Module, for
setting refer to

Chapter 5

)

T2 Core balance transformer:
Earth/Ground Current

5 mA…60 A

Current ratio of core
balance current transformer

1…2 000:1

Output from core balance
current transformer

0…500 mA

Advertising