Functions 3-44

Publication 825-UM001B-EN-P January 2001

Table 3.W Short Circuit Setting Parameters

➊ –5…60

°

C (23…140

°

F)

Earth (Ground) Fault Protection with a Core Balance Current Transformer

This function is integrated into the Cat. No. 825-MST option card. Refer to page

3-28

.

Stalling During Start

Function

If the motor stalls during the starting phase, the motor heats up very rapidly reaching the
temperature limit of the insulation after the permissible stalling time. Large, low-voltage
motors, and especially medium- to high-voltage motors often have short, permissible stalling
times, although their starts may be considerably longer. Accordingly, the permissible stalling
time must be set higher on the basic unit in these instances. With an external speedometer or
zero speed switch, the Smart Motor Manager recognizes that stalling has occurred during
starting, and it switches the motor off immediately. Thus, the motor and the driven
installation are not exposed to unnecessary or unacceptable stress from stalling.

Trip

Function

Factory setting

Off

Response Level

Setting range

4…12

,

e

Factory setting

10

,

e

Setting increments

0.5

,

e

Tripping Delay

Setting range

20…990 ms

Factory setting

50 ms

Setting increments

10 ms

Output Relay

Selection (relays)

#1, No output relay

Factory setting

#1