Error Diagnosis and Troubleshooting 8-9
Publication 825-UM001B-EN-P January 2001
Other Trips
Indication
•
LCD: Does not display the type of the trip (LCD active)
•
Red LED: ON
Cause for this Condition:
If the tripped protection function has been switched “OFF”, before the trip has been reset,
then the trip can not be reset the normal way.
How to Reset
•
Go to RECORDED VALUES mode
•
Go to “CAUSE LAST TRIP” e.g., “ASYMMETRY TRIP”
•
Go to SET VALUES mode
•
Go to tripped Protection Function e.g., “ASYMMETRY TRIP”
•
Switch Protection Function on e.g., “ASYMMETRY TRIP” “ON”
•
Reset Trip: Red LED goes off
•
Switch Protection Function off, if not required