Figure 3.26, Stalling during starting, Table 3.x – Rockwell Automation 825 Smart Motor Manager User Manual User Manual
Page 78: Stalling during start setting parameters, Applications

3-45 Functions
Publication 825-UM001B-EN-P January 2001
Applications
•
Large low-voltage motors
•
Medium- and high-voltage motors
•
Conveyor systems
•
Mills
•
Mixers
•
Crushers
•
Saws
•
Cranes
•
Hoists, etc.
Figure 3.26 Stalling During Starting
Table 3.X Stalling during Start Setting Parameters
Trip
Function
Factory setting
Off
Tripping Delay
Factory setting
The trip time t
sp
depends on the trip time t
ov
chosen for the overcurrent as
follows: t
ov
< 400 ms, t
sp
= 600 ms.; t
ov
≥
400 ms, t
sp
= t
ov
+ 400 ms.
Actuation
Message from zero speed switch to control input #1
Motor running
24V AC/DC at control input #1
Motor standstill
0V AC/DC at control input #1
Output Relay
Selection (relays)
Same relay as for function “High Overload and Jam”
(settable only there)
t
v
I
1
2
I
e
t
I
e
I
1
Normal start without
hindrance by high
overload or stalling
2
Stalling during standing
t
v
Tripping delay