3-45 Functions

Publication 825-UM001B-EN-P January 2001

Applications

Large low-voltage motors

Medium- and high-voltage motors

Conveyor systems

Mills

Mixers

Crushers

Saws

Cranes

Hoists, etc.

Figure 3.26 Stalling During Starting

Table 3.X Stalling during Start Setting Parameters

Trip

Function

Factory setting

Off

Tripping Delay

Factory setting

The trip time t

sp

depends on the trip time t

ov

chosen for the overcurrent as

follows: t

ov

< 400 ms, t

sp

= 600 ms.; t

ov

400 ms, t

sp

= t

ov

+ 400 ms.

Actuation

Message from zero speed switch to control input #1
Motor running

24V AC/DC at control input #1

Motor standstill

0V AC/DC at control input #1

Output Relay

Selection (relays)

Same relay as for function “High Overload and Jam”

(settable only there)

t

v

I

1

2

I

e

t

I

e

I

1

Normal start without
hindrance by high
overload or stalling

2

Stalling during standing

t

v

Tripping delay